Skip to main content
Schneider Electric LC1BP34F40

Schneider Electric LC1BP34F40

MPNLC1BP34F40
Obsolete

bar-mounted contactor - TeSys LC1-BP - 4P - AC-1 1000 V 2000 A - coil 110 VAC

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1BP34F40 key specifications
ParameterValue
Coil typeStandard
Control circuit typeAC
Auxiliary contacts typeInstantaneous 4 NO
Product or component typeContactor
Coil voltage110 V AC 50...400 Hz
Voltage1000 V - power circuit IEC 60158-1 1000 V - power circuit IEC 60947-4 1500 V - power circuit VDE 0110 group C
Control circuit voltage limitsOperational: 0.85...1.1 Uc Drop-out: 0.35...0.5 Uc
[Ue] rated operational voltagePower circuit <= 1000 V AC 50/60 Hz
Breaking capacity12000 A at 500 V for power circuit conforming to IEC 60158-1 12000 A at 500 V for power circuit conforming to IEC 60947-4 15000 A at 440 V for power circuit conforming to IEC 60158-1 15000 A at 440 V for power circuit conforming to IEC 60947-4 5000 A at 1000 V for power circuit conforming to IEC 60158-1 5000 A at 1000 V for power circuit conforming to IEC 60947-4 9000 A at 660...690 V for power circuit conforming to IEC 60158-1 9000 A at 660...690 V for power circuit conforming to IEC 60947-4
[Ie] rated operational current2000 A (at <104 °F (40 °C)) AC AC-1 for power circuit
[Ith] conventional free air thermal current2000 A (at 104 °F (40 °C)) for power circuit
Inrush power in1600 VA

All specifications

LC1BP34F40 additional specifications
ParameterValue
Power dissipation per pole520 W AC-1 - Ith 2000 A
Rated operational power in200 W 500 V AC 1000000 cycles - control circuit 230 W 440 V AC 1000000 cycles - control circuit 250 W 110 V AC 1000000 cycles - control circuit 250 W 220 V AC 1000000 cycles - control circuit
Hold-in power consumption in47 VA
Poles description4P
Pole contact composition4 NO
Utilisation categoryAC-1
Connections - terminalsPower circuit bars 3 x 100 x 5 mm
Operating altitude9842.52 ft (3000 m) without derating
Depth43.1 in (1095 mm)
Width18.7 in (475 mm)
Height19.7 in (500 mm)
Mechanical durability1200000 cycles
StandardsVDE 0660 IEC 60158-1 BS 5424 IEC 60947-4 NF C 63-110
RangeTeSys
Category18402-WORLD SERVICE PARTS(CONTROL ACCESS)
Operating time100...150 ms closing 20...40 ms opening
Protective coverWith
Average impedance0.13 mOhm - Ith 2000 A 50 Hz for power circuit
Device short nameLC1BP
Tightening torquePower circuit 309.8 lbf.in (35 N.m) bars
Protective treatmentTC TH
Contactor applicationMotor-heating-lighting
Associated fuse rating1600 A aM at 2000 A gI at <= 440 V for power circuit
Maximum operating rate120 cyc/h 131 °F (55 °C)
Irms rated making capacity15000 A at 1000 V AC for power circuit conforming to IEC 60158-1 15000 A at 1000 V AC for power circuit conforming to IEC 60947-4
Auxiliary contact composition4 NO
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
MPN
LC1BP34F40