Skip to main content
Schneider Electric LC1BR33ED22

Schneider Electric LC1BR33ED22

MPNLC1BR33ED22
Obsolete

bar-mountedcontactor-TeSysLC1-BR-3P-AC-31000V2750A-coil48VDC

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1BR33ED22 key specifications
ParameterValue
Coil typeStandard
Control circuit typeDC
Auxiliary contacts typetype instantaneous 2 NO + 2 NC
Product or component typeContactor
Coil voltage48 V DC
Voltage1000 V - for power circuit conforming to IEC 60158-1 1000 V - for power circuit conforming to IEC 60947-4 1500 V - for power circuit conforming to VDE 0110 group C
Control circuit voltage limitsOperational: 0.85...1.1 Uc Drop-out: 0.4...0.5 Uc
[Ue] rated operational voltagePower circuit: <= 1000 V AC 50/60 Hz
Breaking capacity11000 A at 660...690 V for power circuit conforming to IEC 60158-1 11000 A at 660...690 V for power circuit conforming to IEC 60947-4 15000 A at 500 V for power circuit conforming to IEC 60158-1 15000 A at 500 V for power circuit conforming to IEC 60947-4 18000 A at 440 V for power circuit conforming to IEC 60158-1 18000 A at 440 V for power circuit conforming to IEC 60947-4 6000 A at 1000 V for power circuit conforming to IEC 60158-1 6000 A at 1000 V for power circuit conforming to IEC 60947-4
[Ie] rated operational current2750 A (at 1800 A (at <40 °C) AC AC-3 for power circuit
[Ith] conventional free air thermal current2750 A (at 40 °C) for power circuit
Motor power500 kW at 220...230 V AC 50/60 Hz 750 kW at 1000 V AC 50/60 Hz 900 kW at 380...400 V AC 50/60 Hz 900 kW at 415 V AC 50/60 Hz 900 kW at 440 V AC 50/60 Hz 900 kW at 500 V AC 50/60 Hz 900 kW at 660...690 V AC 50/60 Hz

All specifications

LC1BR33ED22 additional specifications
ParameterValue
Inrush power in1100 W
Power dissipation per pole680 W AC-1 - Ith 2750 A
Rated operational power in200 W at 500 V AC - electrical durability: 1000000 cycles - for control circuit 230 W at 440 V AC - electrical durability: 1000000 cycles - for control circuit 250 W at 110 V AC - electrical durability: 1000000 cycles - for control circuit 250 W at 220 V AC - electrical durability: 1000000 cycles - for control circuit
Hold-in power consumption in31 W
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-3 AC-1
Connections - terminalsPower circuit: bars 4 x - busbar cross section: 100 x 5 mm
Operating altitude3000 m without derating
Depth915 mm
Width475 mm
Height555 mm
Mechanical durability1200000 cycles
StandardsIEC 60947-4 NF C 63-110 IEC 60158-1 BS 5424 VDE 0660
RangeTeSys
Operating time100...150 ms closing 20...40 ms opening
Protective coverWith
Average impedance0.09 mOhm - Ith 2750 A 50 Hz for power circuit
Device short nameLC1BR
Tightening torquePower circuit: 35 N.m - on bars
Protective treatmentTC TH
Contactor applicationMotor-heating-lighting
Associated fuse rating2000 A aM at 2400 A gI at <= 440 V for power circuit
Maximum operating rate120 cyc/h 55 °C
Irms rated making capacity18000 A at 1000 V AC for power circuit conforming to IEC 60158-1 18000 A at 1000 V AC for power circuit conforming to IEC 60947-4
Auxiliary contact composition2 NO + 2 NC
Ambient air temperature for storage-60...80 °C
Ambient air temperature for operation-5...55 °C
MPN
LC1BR33ED22