Skip to main content
Schneider Electric LC1D123B7

Schneider LC1D123B7 TeSys Deca contactor, 12 A, 24 VAC coil

MPNLC1D123B7
Active

Schneider LC1D123B7 60 100 Va Industrial Control Transformers — now discontinued, supplied from remaining surplus and broker stock.

$145.59Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1D123B7 key specifications
ParameterValue
Range of productTeSys Deca
Product or component typeContactor
Climatic withstandIACS E10 exposure to damp heat IEC 60947-1 Annex Q category D exposure to damp heat
[Ue] rated operational voltagePower circuit Power circuit 10 MOhm for signalling circuit
Poles description3P
Utilisation categoryAC-1 AC-4 AC-3 AC-3e
IP degree of protectionIP20 front face IEC 60529
Mounting supportPlate Rail
Operating altitude0...9842.52 ft (0...3000 m)
Depth3.4 in (86 mm)
Width1.8 in (45 mm)
Height3.9 in (99 mm)

All specifications

LC1D123B7 additional specifications
ParameterValue
StandardsCSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ CSA C22.2 No 60947-4-1
CategoryUS10I1222354
Fire resistance1562 °F (850 °C) IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Non-overlap time1.5 ms on de-energisation between NC and NO contact 1.5 ms on energisation between NC and NO contact
Device short nameLC1D
Protective treatmentTHIEC 60068-2-30
Contactor applicationMotor control Resistive load
Mechanical robustnessVibrations contactor open 2 Gn, 5...300 Hz) Vibrations contactor closed 4 Gn, 5...300 Hz) Shocks contactor open 10 Gn for 11 ms) Shocks contactor closed 15 Gn for 11 ms)
Permissible ambient air temperature around the device-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating

Product details

Overview

Certified to IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 14, and CCC, it meets the compliance documentation required for panel acceptance across North American and international installations.

The AC-3 rating of 12 A covers motor starting and running for a 7.5 hp load; the AC-1 resistive rating of 25 A means the same contactor can switch heater banks or lighting at nearly double the current. For a panel originally specified around the 9070TF75D14 control transformer, note that the LC1D123B7 is a contactor, not a transformer — it switches the load, not steps voltage — so the transformer remains a separate component.

MPN
LC1D123B7