Overview
The LC1D383P7 is a Schneider TeSys Deca 3-pole contactor rated 38 A in AC-3 duty, energised by a 230 V AC coil, and sealed to IP2X.

Schneider Electric TeSys Deca LC1D383P7 contactor, 3-pole, 38 A AC-3 rating, 230 V AC coil, IP2X, rail/plate mount, discontinued.
| Parameter | Value |
|---|---|
| Range of product | TeSys Deca |
| Product or component type | Contactor |
| Climatic withstand | conforming to IACS E10 exposure to damp heat conforming to IEC 60947-1 Annex Q category D exposure to damp heat |
| [Ue] rated operational voltage | Power circuit: 10 MOhm for control circuit |
| Poles description | 3P |
| Utilisation category | AC-3 AC-1 AC-3e |
| IP degree of protection | IP2X conforming to IEC 60529 IP2X conforming to VDE 0106 |
| Mounting support | Rail Plate |
| Operating altitude | 3000 m without derating |
| Depth | 92 mm |
| Width | 45 mm |
| Height | 85 mm |
| Parameter | Value |
|---|---|
| Standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 60947-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ CSA C22.2 No 60947-4-1 |
| Range | TeSys TeSys Deca |
| Fire resistance | 850 °C conforming to IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts |
| Device short name | LC1D |
| Contactor application | Resistive load Motor control |
| Mechanical robustness | Shocks contactor closed (15 Gn for 11 ms) Shocks contactor opened (8 Gn for 11 ms) Vibrations contactor opened (2 Gn, 5...300 Hz) Vibrations contactor closed (4 Gn, 5...300 Hz) |
| Permissible ambient air temperature around the device | -5...60 °C -40...70 °C at Uc |
The LC1D383P7 is a Schneider TeSys Deca 3-pole contactor rated 38 A in AC-3 duty, energised by a 230 V AC coil, and sealed to IP2X.
No related articles