Schneider Electric LC1D65004T6
MPNLC1D65004T6
Active
contactor TeSys Deca - 4 poles - AC-1 690 V 80 A - coil 480 V AC
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Range of product | TeSys D TeSys Deca |
| Product or component type | Contactor |
| [Ue] rated operational voltage | Power circuit 690 V AC 25...400 Hz |
| [Ie] rated operational current | 80 A (at 10 MOhm for control circuit |
| Poles description | 4P |
| Utilisation category | AC-1 |
| IP degree of protection | IP2X VDE 0106 |
| Mounting support | Plate Rail |
| Operating altitude | 9842.52 ft (3000 m) without derating |
| Depth | 5.1 in (130 mm) |
| Width | 3.3 in (85 mm) |
| Height | 4.8 in (122 mm) |
All specifications
| Parameter | Value |
|---|---|
| Standards | EN/IEC 60947-4-1 UL 508 EN/IEC 60947-5-1 CSA C22.2 No 14 |
| Category | 22357-CTR,TESYS D,OPEN,40-65A AC |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Non-overlap time | 1.5 ms on de-energisation between NC and NO contacts 1.5 ms on energisation between NC and NO contacts |
| Device short name | LC1D |
| Protective treatment | THIEC 60068-2-30 |
| Contactor application | Resistive load |
| Mechanical robustness | Shocks contactor opened 15 gn) Shocks contactor closed Vibrations contactor opened Vibrations contactor closed |
| Permissible ambient air temperature around the device | -76...176 °F (-60...80 °C) storage -40...140 °F (-40...60 °C) operation 140...158 °F (60...70 °C) with derating |
MPN