Skip to main content
Schneider Electric LC1D80004M7

Schneider LC1D80004M7 TeSys Deca 4-Pole AC-1 Contactor

MPNLC1D80004M7
Active

Schneider Electric TeSys Deca LC1D80004M7, 4-pole contactor, AC-1 resistive load, 22-55 kW motor power, coil AC 50/60 Hz, 125 mm depth.

$705.00Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1D80004M7 key specifications
ParameterValue
Range of productTeSys Deca
Control circuit typeAC 50/60 Hz
Product or component typeContactor
Climatic withstandIACS E10 exposure to damp heat
Coil voltage220 V AC 50/60 Hz
VoltagePower circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1
Control circuit voltage limits0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational AC 60 Hz 0.3...0.6 Uc (-40...158 °F (-40...70 °C)):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...131 °F (-40...55 °C)):operational AC 50 Hz 1...1.1 Uc (131...158 °F (55...70 °C)):operational AC 50/60 Hz
[Ue] rated operational voltagePower circuit Power circuit <= 690 V AC
[Uimp] rated impulse withstand voltage8 kV IEC 60947
[Icw] rated short-time withstand current640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit 135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit
Breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Ie] rated operational current125 A (at 80 A (at 80 A (at 55 A (at <140 °F (60 °C)) at <= 400 V AC AC-4 for power circuit

All specifications

LC1D80004M7 additional specifications
ParameterValue
[Ith] conventional free air thermal current125 A (at 140 °F (60 °C)) for power circuit
Motor power22 kW at 220...230 V AC 50/60 Hz 37 kW at 380...400 V AC 50/60 Hz 45 kW at 660...690 V AC 50/60 Hz 55 kW at 500 V AC 50/60 Hz 45 kW at 415...440 V AC 50/60 Hz
Inrush power in245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Power dissipation per pole12.5 W AC-1
Hold-in power consumption in26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) 26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Poles description4P
Pole contact composition4 NO
Utilisation categoryAC-1
IP degree of protectionIP20 front face IEC 60529
Mounting supportRail Plate
Connections - terminalsControl circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible without cable end Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: flexible without cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible with cable end Power circuit: connector 2 0.006...0.02 in² (4...16 mm²) - cable stiffness: flexible with cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: solid without cable end Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: solid without cable end
Pollution degree3
Operating altitude0...9842.52 ft (0...3000 m)
Depth4.9 in (125 mm)
Width3.8 in (96 mm)
Height5 in (127 mm)
Electrical durability0.8 Mcycles 125 A AC-1 <= 440 V
Mechanical durability4 Mcycles
StandardsEN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 CSA C22.2 No 14 UL 60947-4-1 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ IEC 60335-1:Clause 30.2
RangeTeSys
CategoryUS10I1222359
Operating time20...35 ms closing 6...20 ms opening
Coil technologyWithout built-in suppressor module
Fire resistance1562 °F (850 °C) IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation6...10 W at 50/60 Hz
Protective coverWith
Average impedance0.8 mOhm - Ith 125 A 50 Hz for power circuit
Device short nameLC1D
Tightening torqueControl circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm) Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals pozidriv No 2
Compatibility codeLC1D
Overvoltage categoryIII
Protective treatmentTHIEC 60068-2-30
Contactor applicationResistive load
Mechanical robustnessVibrations contactor open 2 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor closed 10 Gn for 11 ms)
Associated fuse rating200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit
Maximum operating rate3600 cyc/h at 60 °C
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity1100 A at 440 V for power circuit conforming to IEC 60947
Permissible ambient air temperature around the device-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating

Product details

It occupies a 125 mm deep by 96 mm wide footprint on rail or plate mounting, with a height of 127 mm. The coil is AC 50/60 Hz without a built-in suppressor module, drawing 245 VA inrush at 20 °C. Motor power capability spans 22 kW at 230 V up to 55 kW at 500 V, making it suitable for medium-duty switching stations or panel feeders.

The 4 NO poles handle full resistive load at rated breaking capacity of 1100 A at 440 V (IEC 60947). Electrical durability is 0.8 Mcycles under AC-1 at 125 A, while mechanical endurance hits 4 Mcycles. Power circuit torque needs 12 N.m — a 6–8 mm flat or 4 mm hex driver. Control wiring accepts 1–4 mm² flexible or solid, torque 1.2 N.m. Operating rate is 3600 cycles/hour at 60 °C, with heat dissipation 6–10 W. The TH treatment (IEC 60068-2-30) means it handles damp heat exposure. Altitude rating goes to 3000 m without derating. These numbers define the thermal and environmental headroom for continuous use.

This contactor carries full third-party certification: UL 60947-4-1, CSA C22.2 No 14, IEC 60947-4-1 and -5-1. Fire resistance tested at 850 °C (IEC 60695-2-1) and flame retardance V1 per UL 94. The IP20 front face protects against finger contact. All relevant IEC 60335-2-40 annexes for appliance applications are also covered. Documentation (datasheet, installation manual, CE declaration) is available per request on the RFQ.

Frequently asked questions

What is LC1D80004M7's listed depth?

The depth is 4.9 in (125 mm).

What is LC1D80004M7's listed range?

It belongs to the TeSys range, specifically the TeSys Deca series.

What compliance documentation does this brand provide for LC1D80004M7?

The contactor complies with IEC 60947-4-1, IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 14, and related appliance standards IEC 60335-2-40. It also meets fire resistance at 850 °C and V1 flame retardance.

MPN