Skip to main content
Schneider Electric LC1D80008F5

Schneider Electric LC1D80008F5

MPNLC1D80008F5
Obsolete

TeSys D contactor - 4P(2 NO + 2 NC) - AC-1 <= 440 V 125 A - 110 V AC 50 Hz coil

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1D80008F5 key specifications
ParameterValue
Range of productTeSys Deca
Control circuit typeAC 50 Hz
Product or component typeContactor
Climatic withstandIACS E10 exposure to damp heat
Coil voltage110 V AC 50 Hz
VoltagePower circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1
Control circuit voltage limits0.3...0.6 Uc (-40...158 °F (-40...70 °C)):drop-out AC 50 Hz 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational AC 50 Hz 1...1.1 Uc (131...158 °F (55...70 °C)):operational AC 50 Hz
[Ue] rated operational voltagePower circuit Power circuit <= 690 V AC 25...400 Hz
[Uimp] rated impulse withstand voltage8 kV IEC 60947
[Icw] rated short-time withstand current640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit 135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit
Breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Ie] rated operational current125 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit

All specifications

LC1D80008F5 additional specifications
ParameterValue
[Ith] conventional free air thermal current125 A (at 140 °F (60 °C)) for power circuit
Inrush power in200 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Power dissipation per pole12.5 W AC-1
Hold-in power consumption in20 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Poles description4P
Pole contact composition2 NO + 2 NC
Utilisation categoryAC-1
IP degree of protectionIP20 front face IEC 60529
Mounting supportPlate Rail
Connections - terminalsControl circuit: screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.004 in² (1...2.5 mm²) - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) - cable stiffness: solid without cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible without cable end Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: flexible without cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: flexible with cable end Power circuit: connector 2 0.006...0.02 in² (4...16 mm²) - cable stiffness: flexible with cable end Power circuit: connector 1 0.006...0.08 in² (4...50 mm²) - cable stiffness: solid without cable end Power circuit: connector 2 0.006...0.04 in² (4...25 mm²) - cable stiffness: solid without cable end
Pollution degree3
Operating altitude0...9842.52 ft (0...3000 m)
Depth5.5 in (140 mm)
Width3.8 in (96 mm)
Height5 in (127 mm)
Electrical durability0.8 Mcycles 125 A AC-1 <= 440 V
Mechanical durability10 Mcycles
StandardsCSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
RangeTeSys
Category22359-CTR,TESYS D,OPEN,80-150A AC&DC
Operating time20...35 ms closing 6...20 ms opening
Coil technologyWithout built-in suppressor module
Fire resistance1562 °F (850 °C) IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation6...10 W at 50 Hz
Protective coverWithout
Average impedance0.8 mOhm - Ith 125 A 50 Hz for power circuit
Device short nameLC1D
Tightening torqueControl circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
Compatibility codeLC1D
Overvoltage categoryIII
Protective treatmentTHIEC 60068-2-30
Contactor applicationResistive load
Mechanical robustnessVibrations contactor open 2 Gn, 5...300 Hz) Shocks contactor open 8 Gn for 11 ms) Vibrations contactor closed 3 Gn, 5...300 Hz) Shocks contactor closed 10 Gn for 11 ms)
Associated fuse rating200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity1100 A at 440 V for power circuit conforming to IEC 60947
Permissible ambient air temperature around the device-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating
MPN
LC1D80008F5