Skip to main content
Schneider Electric LC1E250M7

Schneider Electric LC1E250M7

MPNLC1E250M7
Active

Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3/AC-3e,<=440V,250A/190A,220V AC coil,50/60Hz

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1E250M7 key specifications
ParameterValue
Range of productEasy TeSys Control
Control circuit typeAC at 50/60 Hz standard
Product or component typeContactor
Coil voltage220 V AC 50/60 Hz
Voltage690 V conforming to IEC 60947-4-1
Control circuit voltage limits0.85...1.1 Uc (-5...55 °C):operational 50/60 Hz 0.35...0.55 Uc (-5...55 °C):drop-out 50/60 Hz
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV coil not connected to the power circuit conforming to IEC 60947
[Icw] rated short-time withstand current1800 A 40 °C - 10 s for power circuit
Breaking capacity2000 A at 440 V for power circuit conforming to IEC 60947
[Ie] rated operational current250 A (at 190 A (at 300 A (at <40 °C) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current300 A (at 40 °C) for power circuit

All specifications

LC1E250M7 additional specifications
ParameterValue
Motor power75 kW at 220/230 V AC 50/60 Hz 132 kW at 380/400 V AC 50/60 Hz 140 kW at 415/440 V AC 50/60 Hz 160 kW at 500 V AC 50/60 Hz 160 kW at 660/690 V AC 50/60 Hz 160 kW at 660...690 V AC 50/60 Hz
Inrush power in950...1180 VA 40...400 Hz (at 20 °C)
Power dissipation per pole20 W AC-3 29 W AC-1
Hold-in power consumption in8.9...10.9 VA 40...400 Hz (at 20 °C)
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-3 AC-3e AC-1
IP degree of protectionIP00 conforming to IEC 60529
Mounting supportPlate
Connections - terminalsPower circuit: cable with lug 2 - external diameter: 185 mm - busbar cross section: 32 x 4 mm Power circuit: bars 2 - external diameter: 185 mm - busbar cross section: 32 x 4 mm Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid without cable end
Pollution degree3
Operating altitude3000 m without derating
Depth181 mm
Width168.5 mm
Height197 mm
Product weight4.7 kg
Electrical durability700000 cycles AC-3 200000 cycles AC-1
Mechanical durability5000000 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 GB/T 14048.1 GB/T 14048.4
RangeEasy TeSys
Operating time20...35 ms on closing 130 ms on opening
Fire resistance850 °C conforming to IEC 60695-2-1
Heat dissipation8...9.8 W
Average impedance0.32 mOhm - Ith 300 A 50 Hz for power circuit
Device short nameLC1E
Tightening torquePower circuit: 35 N.m Control circuit: 1.2 N.m
Overvoltage categoryIII
Contactor applicationMotor control Resistive load
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Associated fuse rating315 A gG at <= 690 V coordination type 1 for power circuit
Maximum operating rate1200 cyc/h 55 °C
Irms rated making capacity2500 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Auxiliary contact compositionWithout
Permissible ambient air temperature around the device-5...55 °C operation -20...70 °C at Uc -60...80 °C storage
MPN
LC1E250M7