Skip to main content
Schneider Electric LC1E300M5

Schneider Electric LC1E300M5

MPNLC1E300M5
Active

Contactor,Easy TeSys Control,LC1E,3P(3NO),AC-3/AC-3e,<=440V,300A/265A,220V AC coil,50Hz

$366.71Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1E300M5 key specifications
ParameterValue
Range of productEasy TeSys Control
Control circuit typeAC at 50 Hz
Product or component typeContactor
Coil voltage220 V AC 50 Hz
Voltage690 V conforming to IEC 60947-4-1
Control circuit voltage limits0.85...1.1 Uc (-5...55 °C):operational 50 Hz 0.35...0.55 Uc (-5...55 °C):drop-out 50 Hz
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV coil not connected to the power circuit conforming to IEC 60947
[Icw] rated short-time withstand current2650 A 40 °C - 10 s for power circuit
Breaking capacity2400 A at 440 V for power circuit conforming to IEC 60947
[Ie] rated operational current300 A (at 265 A (at 320 A (at <40 °C) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current320 A (at 40 °C) for power circuit

All specifications

LC1E300M5 additional specifications
ParameterValue
Motor power90 kW at 220/230 V AC 50/60 Hz 160 kW at 380/400 V AC 50/60 Hz 160 kW at 415 V AC 50/60 Hz 185 kW at 440 V AC 50/60 Hz 200 kW at 500 V AC 50/60 Hz 220 kW at 660/690 V AC 50/60 Hz
Inrush power in650 VA 50 Hz cos phi 0.9 (at 20 °C) 650 VA 60 Hz cos phi 0.9 (at 20 °C)
Power dissipation per pole27 W AC-3 31 W AC-1
Hold-in power consumption in10 VA 50 Hz cos phi 0.9 (at 20 °C) 10 VA 60 Hz cos phi 0.9 (at 20 °C)
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-3 AC-3e AC-1
IP degree of protectionIP00 conforming to IEC 60529
Mounting supportPlate
Connections - terminalsPower circuit: cable with lug 1 1...4 mm² - external diameter: 240 mm - cable stiffness: flexible without cable end Power circuit: bars 2 1...4 mm² - cable stiffness: flexible without cable end - busbar cross section: 5 x 30 mm Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - external diameter: 240 mm - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid without cable end - busbar cross section: 5 x 30 mm
Pollution degree3
Operating altitude3000 m without derating
Depth219 mm
Width213 mm
Height206 mm
Product weight8.5 kg
Electrical durability400000 cycles AC-1 500000 cycles AC-3
Mechanical durability5000000 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 GB/T 14048.1 GB/T 14048.4
RangeEasy TeSys
Operating time40...65 ms on closing 100...170 ms on opening
Fire resistance850 °C conforming to IEC 60695-2-1
Heat dissipation8 W for control circuit
Average impedance0.3 mOhm - Ith 320 A 50 Hz for power circuit
Device short nameLC1E
Tightening torqueControl circuit: 1.2 N.m Power circuit: 35 N.m
Overvoltage categoryIII
Contactor applicationMotor control Resistive load
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Vibrations contactor closed (3 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Shocks contactor closed (7 Gn for 11 ms)
Associated fuse rating500 A gG at <= 690 V coordination type 1 for power circuit
Maximum operating rate1200 cyc/h 55 °C
Irms rated making capacity3000 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Auxiliary contact compositionWithout
Permissible ambient air temperature around the device-20...70 °C at Uc -60...80 °C storage -5...55 °C operation
MPN