Skip to main content
Schneider Electric LC1E400Q7

Schneider Electric LC1E400Q7

MPNLC1E400Q7
Active

EasyPact TVS contactor 3P(3 NO) - AC-3 - <= 440 V 400A - 380 V AC coil

$56.16Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1E400Q7 key specifications
ParameterValue
Range of productEasy TeSys Control
Control circuit typeAC at 50/60 Hz
Product or component typeContactor
Coil voltage380 V AC 50/60 Hz
Voltage690 V conforming to IEC 60947-4-1
Control circuit voltage limits0.85...1.1 Uc (-5...55 °C):operational 50/60 Hz 0.35...0.5 Uc (-5...55 °C):drop-out 50/60 Hz
[Ue] rated operational voltagePower circuit: <= 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV coil not connected to the power circuit conforming to IEC 60947
[Icw] rated short-time withstand current3600 A 40 °C - 10 s for power circuit
Breaking capacity3200 A at 440 V for power circuit conforming to IEC 60947
[Ie] rated operational current400 A (at 330 A (at 500 A (at <40 °C) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current500 A (at 40 °C) for power circuit

All specifications

LC1E400Q7 additional specifications
ParameterValue
Motor power110 kW at 220/230 V AC 50/60 Hz 200 kW at 380/400 V AC 220 kW at 415 V AC 250 kW at 440 V AC 257 kW at 500 V AC 280 kW at 660/690 V AC
Inrush power in1075 VA 50 Hz cos phi 0.9 (at 20 °C) 1075 VA 60 Hz cos phi 0.9 (at 20 °C)
Power dissipation per pole42 W AC-3 65 W AC-1
Hold-in power consumption in15 VA 50 Hz cos phi 0.9 (at 20 °C) 15 VA 60 Hz cos phi 0.9 (at 20 °C)
Poles description3P
Pole contact composition3 NO
Utilisation categoryAC-3 AC-3e AC-1
IP degree of protectionIP00 conforming to IEC 60529
Mounting supportPlate
Connections - terminalsPower circuit: cable with lug 2 1...4 mm² - external diameter: 150 mm - cable stiffness: flexible without cable end Power circuit: bars 2 1...4 mm² - cable stiffness: flexible without cable end - busbar cross section: 30 x 5 mm Control circuit: screw clamp terminals 1 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: flexible without cable end Control circuit: screw clamp terminals 2 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...2.5 mm² - cable stiffness: flexible with cable end Control circuit: screw clamp terminals 1 1...4 mm² - external diameter: 150 mm - cable stiffness: solid without cable end Control circuit: screw clamp terminals 2 1...4 mm² - cable stiffness: solid without cable end - busbar cross section: 30 x 5 mm
Pollution degree3
Operating altitude3000 m without derating
Depth219 mm
Width213 mm
Height375 mm
Product weight9.1 kg
Electrical durability250000 cycles AC-1 600000 cycles AC-3
Mechanical durability4000000 cycles
StandardsEN/IEC 60947-1 EN/IEC 60947-4-1 GB/T 14048.1 GB/T 14048.4
RangeEasy TeSys
Operating time100...170 ms on opening 40...75 ms on closing
Fire resistance850 °C conforming to IEC 60695-2-1
Heat dissipation14 W for control circuit
Average impedance0.26 mOhm - Ith 500 A 50 Hz for power circuit
Device short nameLC1E
Tightening torqueControl circuit: 1.2 N.m Power circuit: 35 N.m
Overvoltage categoryIII
Contactor applicationMotor control Resistive load
Mechanical robustnessVibrations contactor open (1.5 Gn, 5...300 Hz) Shocks contactor open (6 Gn for 11 ms) Vibrations contactor closed (5 Gn, 5...300 Hz) Shocks contactor closed (15 Gn for 11 ms)
Associated fuse rating630 A gG at <= 690 V coordination type 1 for power circuit
Maximum operating rate2400 cyc/h 55 °C
Irms rated making capacity4000 A at 440 V AC for power circuit conforming to IEC 60947-4-1
Auxiliary contact compositionWithout
Permissible ambient air temperature around the device-20...70 °C at Uc -60...80 °C storage -5...55 °C operation
MPN