MPNLC1F225F6
Obsolete

TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 225 A - coil 110 V AC

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1F225F6 key specifications
ParameterValue
Range of productTeSys F
Control circuit typeAC 60 Hz
Product or component typeContactor
Coil voltage110 V AC 60 Hz
Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Control circuit voltage limitsOperational 0.85...1.1 Uc 50/60 Hz 131 °F (55 °C)) Drop-out 0.35...0.55 Uc 50/60 Hz 131 °F (55 °C))
[Ue] rated operational voltage<= 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current1800 A 104 °F (40 °C) - 10 s 1000 A 104 °F (40 °C) - 30 s 850 A 104 °F (40 °C) - 1 min 560 A 104 °F (40 °C) - 3 min 440 A 104 °F (40 °C) - 10 min
Breaking capacity1800 A conforming to IEC 60947-4-1
[Ie] rated operational current315 A (at 225 A (at <131 °F (55 °C)) at <= 440 V AC-3
[Ith] conventional free air thermal current315 A (at 104 °F (40 °C))

All specifications

LC1F225F6 additional specifications
ParameterValue
Motor power110 kW at 380...400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660...690 V AC 50/60 Hz (AC-3) 63 kW at 220...230 V AC 50/60 Hz (AC-3) 40 kW at 400 V AC 50/60 Hz (AC-4)
Inrush power in970 VA, 60 Hz 0.3 68 °F (20 °C))
Power dissipation per pole32 W AC-1 16 W AC-3
Power pole contact composition3 NO
Hold-in power consumption in66 VA, 60 Hz 0.3 68 °F (20 °C))
Poles description3P
Utilisation categoryAC-3 AC-4 AC-1
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Mounting supportPlate
Connections - terminalsControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 32 x 4 mm Power circuit lugs-ring terminals 1 0.3 in² (185 mm²) Power circuit connector 1 0.3 in² (185 mm²) Power circuit bolted connection
Operating altitude9842.52 ft (3000 m) without derating
Depth7.1 in (181 mm)
Width6.6 in (168.5 mm)
Height7.8 in (197 mm)
Mechanical durability10 Mcycles
StandardsEN 60947-1 IEC 60947-4-1 EN 60947-4-1 JIS C8201-4-1 IEC 60947-1
RangeTeSys
Category22336-CTR,F-LINE,AC,OPEN,NONREV
Operating time20...35 ms closing 7...15 ms opening
Heat dissipation18...24 W
Average impedance0.32 mOhm - Ith 315 A 50 Hz
Device short nameLC1F
Tightening torqueControl circuit 10.6 lbf.in (1.2 N.m) Power circuit 309.8 lbf.in (35 N.m)
Compatibility codeLC1F
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationMotor control Resistive load
Associated fuse rating315 A gG at 250 A aM at <= 440 V
Maximum operating rate2400 cyc/h 131 °F (55 °C)
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C)
MPN