Specifications

LC1F225V5 key specifications
ParameterValue
Range of productTeSys F
Control circuit typeAC at 50 Hz
Product or component typeContactor
Coil voltage400 V AC 50 Hz
Voltage1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C
Control circuit voltage limitsOperational: 0.85...1.1 Uc 50/60 Hz (at 55 °C) Drop-out: 0.35...0.55 Uc 50/60 Hz (at 55 °C)
[Ue] rated operational voltage<= 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current1800 A 40 °C - 10 s 1000 A 40 °C - 30 s 850 A 40 °C - 1 min 560 A 40 °C - 3 min 440 A 40 °C - 10 min
Breaking capacity1800 A conforming to IEC 60947-4-1
[Ie] rated operational current315 A (at 225 A (at <55 °C) at <= 440 V AC-3
[Ith] conventional free air thermal current315 A (at 40 °C)

All specifications

LC1F225V5 additional specifications
ParameterValue
Motor power110 kW at 380...400 V AC 50/60 Hz (AC-3) 110 kW at 415 V AC 50/60 Hz (AC-3) 110 kW at 440 V AC 50/60 Hz (AC-3) 129 kW at 500 V AC 50/60 Hz (AC-3) 129 kW at 660...690 V AC 50/60 Hz (AC-3) 63 kW at 220...230 V AC 50/60 Hz (AC-3) 40 kW at 400 V AC 50/60 Hz (AC-4)
Inrush power in805 VA, 50 Hz cos phi 0.3 (at 20 °C)
Power dissipation per pole32 W AC-1 16 W AC-3
Power pole contact composition3 NO
Hold-in power consumption in55 VA, 50 Hz cos phi 0.3 (at 20 °C)
Poles description3P
Utilisation categoryAC-3 AC-1 AC-4
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Mounting supportPlate
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm Power circuit: lugs-ring terminals 1 cable(s) 185 mm² Power circuit: connector 1 cable(s) 185 mm² Power circuit: bolted connection
Operating altitude3000 m without derating
Depth181 mm
Width168.5 mm
Height197 mm
Product weight4.75 kg
Mechanical durability10 Mcycles
StandardsIEC 60947-4-1 JIS C8201-4-1 EN 60947-1 EN 60947-4-1 IEC 60947-1
RangeTeSys
Operating time20...35 ms closing 7...15 ms opening
Heat dissipation18...24 W
Average impedance0.32 mOhm - Ith 315 A 50 Hz
Device short nameLC1F
Tightening torqueControl circuit: 1.2 N.m Power circuit: 35 N.m
Compatibility codeLC1F
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationMotor control Resistive load
Associated fuse rating315 A gG at 250 A aM at <= 440 V
Maximum operating rate2400 cyc/h 55 °C
Ambient air temperature for storage-60...80 °C
Ambient air temperature for operation-5...55 °C
Permissible ambient air temperature around the device-40...70 °C
MPN
LC1F225V5