Skip to main content
Schneider Electric LC1F265

Schneider LC1F265 TeSys F contactor body, 3-pole, 350 A

MPNLC1F265
Obsolete

Schneider Electric TeSys F LC1F265 contactor body, 3-pole, 350 A switching current, 24 V coil, 8 W power consumption, AC-1/AC-3/AC-4 rated, 0.3 mOhm impedance, IP20, plate mount.

$835.66 – $1,561.70Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F265 key specifications
ParameterValue
Product or component typeContactor
Coil voltage24...1000 V AC 40...400 Hz with LX1/LX9 coil 24...460 V DC with LX4 coil 100...250 V AC 50/60 Hz with LXE coil 100...380 V with LXE coil
Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Control circuit voltage limitsOperational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil Drop-out: 0.35...0.55 Uc AC 40...400 Hz with LX1/LX9 coil Operational: 0.85...1.1 Uc DC with LX4 coil Drop-out: 0.15...0.2 Uc DC with LX4 coil Operational: 85...275 V AC 50/60 Hz with LXE coil Drop-out: 0...60 V AC 50/60 Hz with LXE coil Operational: 85...418 V DC with LXE coil Drop-out: 0...45 V DC with LXE coil
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current2200 A 104 °F (40 °C) - 10 s 1230 A 104 °F (40 °C) - 30 s 950 A 104 °F (40 °C) - 1 min 620 A 104 °F (40 °C) - 3 min 480 A 104 °F (40 °C) - 10 min
Breaking capacity2120 A conforming to IEC 60947-4-1
[Ie] rated operational current350 A 104 °F (40 °C)) 265 A 131 °F (55 °C)) <= 440 V AC AC-3
[Ith] conventional free air thermal current350 A (at 104 °F (40 °C))
Motor power132 kW at 380...400 V AC 50/60 Hz (AC-3) 140 kW at 415 V AC 50/60 Hz (AC-3) 140 kW at 440 V AC 50/60 Hz (AC-3) 147 kW at 1000 V AC 50/60 Hz (AC-3) 160 kW at 500 V AC 50/60 Hz (AC-3) 75 kW at 220...240 V AC 50/60 Hz (AC-3) 160 kW at 660...690 V AC 50/60 Hz (AC-3) 51 kW at 400 V AC 50/60 Hz (AC-4)
Inrush power in600...700 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 655...803 VA (at 68 °F (20 °C))with LX4 coil 300...350 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 300...310 VA (at 68 °F (20 °C))with LXE coil

All specifications

LC1F265 additional specifications
ParameterValue
Power dissipation per pole37 W AC-1 21 W AC-3
Power pole contact composition3 NO
Hold-in power consumption in8...10 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 3.68...4.53 VA (at 68 °F (20 °C))with LX4 coil 4.5...7.0 VA, 50/60 Hz cos phi 0.5 (at 68 °F (20 °C))with LXE coil 2.5...4.0 VA (at 68 °F (20 °C))with LXE coil
Poles description3P
Utilisation categoryAC-3 AC-4 AC-1
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Mounting supportPlate
Connections - terminalsPower circuit bar 2 32 x 4 mm Power circuit lugs-ring terminals 1 0.4 in² (240 mm²) Power circuit connector 1 0.4 in² (240 mm²) Power circuit bolted connection Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)solid without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²) Control circuit screw clamp terminals 1.0 0.0003...0.004 in² (0.2...2.5 mm²)flexible without cable end Control circuit screw clamp terminals 1.0 0.0004...0.004 in² (0.25...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1.0 0.0003...0.004 in² (0.2...2.5 mm²)solid without cable end
Operating altitude9842.52 ft (3000 m) without derating
Depth8.4 in (213 mm)
Width7.9 in (201.5 mm)
Height8.0 in (203 mm)
Mechanical durability10 Mcycles
StandardsIEC 60947-1 IEC 60947-4-1 JIS C8201-4-1 EN 60947-1 EN 60947-4-1
RangeTeSys
CategoryUS10I1222336
Operating time40...65 ms closing with LX1/LX9 coil 100...170 ms opening with LX1/LX9 coil 40...50 ms closing with LX4 coil 40...65 ms opening with LX4 coil 40...80 ms closing with LXE coil 6...54 ms opening with LXE coil
Heat dissipation8 W 2.2...2.5 W
Average impedance0.3 mOhm - Ith 350 A 50 Hz
Device short nameLC1F
Tightening torquePower circuit 309.8 lbf.in (35 N.m) Control circuit 10.6 lbf.in (1.2 N.m) Control circuit 5.3 lbf.in (0.6 N.m)
Compatibility codeLC1F
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationResistive load Motor control
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open6 Gn for 1/2 sine wave (11 ms) Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Associated fuse rating315 A aM at 400 A gG at <= 440 V
Maximum operating rate2400 cyc/h 131 °F (55 °C)
Irms rated making capacity2650 A AC conforming to IEC 60947-4-1
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C)

Product details

Overview

The LC1F265 is a Schneider TeSys F contactor body rated for 350 A switching current across AC-1, AC-3, and AC-4 utilization categories, with a 24 V coil drawing 8 W holding power. The 3-pole design carries a 0.3 mOhm average impedance at 350 A, 50 Hz, and is built for resistive and motor control applications on a 3-phase supply.

Compared to the LC1F115, the LC1F265 switches 350 A versus 200 A, making it the choice for higher-current motor or resistive loads where the LC1F115's 115 A rated current would be undersized.

MPN
LC1F265