Skip to main content
Schneider Electric LC1F5004

Schneider Electric LC1F5004

MPNLC1F5004
Obsolete

CONTACTOR 600VAC|SQD LC1F5004 CONTACTOR 600VAC

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F5004 key specifications
ParameterValue
Product or component typeContactor
Coil voltage48...1000 V AC 40...400 Hz with LX1/LX9 coil 48...440 V DC with LX4 coil
Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Control circuit voltage limitsOperational: 0.85...1.1 Uc AC 40...400 Hz with LX1/LX9 coil Drop-out: 0.3...0.5 Uc AC 40...400 Hz with LX1/LX9 coil Operational: 0.85...1.1 Uc DC with LX4 coil Drop-out: 0.2...0.35 Uc DC with LX4 coil
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current4200 A 104 °F (40 °C) - 10 s 3200 A 104 °F (40 °C) - 30 s 2400 A 104 °F (40 °C) - 1 min 1500 A 104 °F (40 °C) - 3 min 1200 A 104 °F (40 °C) - 10 min
Breaking capacity4000 A conforming to IEC 60947-4-1
[Ie] rated operational current700 A 104 °F (40 °C)) <= 440 V AC AC-1
[Ith] conventional free air thermal current700 A (at 104 °F (40 °C))
Inrush power in1050...1150 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 990...1220 VA (at 68 °F (20 °C))with LX4 coil
Power dissipation per pole88 W AC-1

All specifications

LC1F5004 additional specifications
ParameterValue
Power pole contact composition4 NO
Hold-in power consumption in16...20 VA, 40...400 Hz cos phi 0.9 (at 68 °F (20 °C))with LX1/LX9 coil 4.54...8 VA (at 68 °F (20 °C))with LX4 coil
Poles description4P
Utilisation categoryAC-1
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Mounting supportPlate
Connections - terminalsPower circuit lugs-ring terminals 2 0.4 in² (240 mm²) Power circuit bar 2 40 x 5 mm Power circuit bolted connection Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)solid without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²) Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)
Operating altitude9842.52 ft (3000 m) without derating
Depth9.1 in (232 mm)
Width11.3 in (288 mm)
Height9.4 in (238 mm)
Mechanical durability10 Mcycles
StandardsJIS C8201-4-1 EN 60947-1 IEC 60947-1 EN 60947-4-1 IEC 60947-4-1
RangeTeSys
CategoryUS10I1222336
Operating time40...75 ms closing with LX1/LX9 coil 100...170 ms opening with LX1/LX9 coil 50...60 ms closing with LX4 coil 45...60 ms opening with LX4 coil
Heat dissipation18 W
Average impedance0.18 mOhm - Ith 700 A 50 Hz
Device short nameLC1F
Tightening torquePower circuit 309.8 lbf.in (35 N.m) Control circuit 10.6 lbf.in (1.2 N.m)
Compatibility codeLC1F
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationResistive load
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed4 Gn, 5...300 Hz Shocks contactor open9 Gn for 1/2 sine wave (11 ms) Shocks contactor closed15 Gn for 1/2 sine wave (11 ms)
Associated fuse rating500 A aM at 800 A gG at <= 440 V
Maximum operating rate2400 cyc/h 131 °F (55 °C)
Irms rated making capacity5000 A AC conforming to IEC 60947-4-1
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C)
MPN
LC1F5004