Skip to main content
Schneider Electric LC1F500ED

Schneider Electric LC1F500ED

MPNLC1F500ED
Obsolete

TeSys F contactor - 3P (3 NO) - AC-3 - <= 440 V 500 A - coil 48 V DC

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F500ED key specifications
ParameterValue
Range of productTeSys F
Motor starter typeDirect on-line contactor
Control circuit typeDC standard
Product or component typeContactor
Contactor coil voltage48 V DC standard
Coil voltage48 V DC
Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Control circuit voltage limitsOperational 0.85...1.1 Uc 131 °F (55 °C)) Drop-out 0.2...0.35 Uc 131 °F (55 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current4200 A 104 °F (40 °C) - 10 s 3200 A 104 °F (40 °C) - 30 s 2400 A 104 °F (40 °C) - 1 min 1500 A 104 °F (40 °C) - 3 min 1200 A 104 °F (40 °C) - 10 min
Breaking capacity4000 A conforming to IEC 60947-4-1

All specifications

LC1F500ED additional specifications
ParameterValue
[Ie] rated operational current700 A (at 500 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Ith] conventional free air thermal current700 A (at 104 °F (40 °C))
Motor power250 kW at 380...400 V AC 50/60 Hz (AC-3) 280 kW at 415 V AC 50/60 Hz (AC-3) 295 kW at 440 V AC 50/60 Hz (AC-3) 355 kW at 500 V AC 50/60 Hz (AC-3) 335 kW at 660...690 V AC 50/60 Hz (AC-3) 335 kW at 1000 V AC 50/60 Hz (AC-3) 147 kW at 220...230 V AC 50/60 Hz (AC-3) 80 kW at 400 V AC 50/60 Hz (AC-4)
Inrush power in1100 W 68 °F (20 °C))
Motor power range250...500 kW 380...440 V 3 phase 110...220 kW 380...440 V 3 phase 110...220 kW 200...240 V 3 phase 250...500 kW 480...500 V 3 phase
Power dissipation per pole88 W AC-1 45 W AC-3
Hold-in power consumption in6 W 68 °F (20 °C)
Power pole contact composition3 NO
Poles description3P
Utilisation categoryAC-3 AC-1 AC-4
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Mounting supportPlate
Connections - terminalsControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 40 x 5 mm Power circuit lugs-ring terminals 2 0.4 in² (240 mm²) Power circuit bolted connection
Operating altitude9842.52 ft (3000 m) without derating
Depth9.1 in (232 mm)
Width9.2 in (233 mm)
Height9.4 in (238 mm)
Mechanical durability10 Mcycles
StandardsEN 60947-4-1 EN 60947-1 JIS C8201-4-1 IEC 60947-1 IEC 60947-4-1
RangeTeSys
CategoryUS10I1222331
Operating time50...60 ms closing 45...60 ms opening
Heat dissipation6 W
Average impedance0.18 mOhm - Ith 700 A 50 Hz
Device short nameLC1F
Tightening torqueControl circuit 10.6 lbf.in (1.2 N.m) Power circuit 309.8 lbf.in (35 N.m)
Compatibility codeLC1F
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationMotor control Resistive load
Associated fuse rating500 A aM at 800 A gG at <= 440 V
Maximum operating rate2400 cyc/h 131 °F (55 °C)
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C)
MPN
LC1F500ED