Skip to main content
Schneider Electric LC1F500F7

Schneider Electric LC1F500F7

MPNLC1F500F7
Obsolete

CONTACTOR 600VAC 500AMP IEC +OPTIONS|CONTACTOR 600VAC 500AMP IEC +OPTIONS

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1F500F7 key specifications
ParameterValue
Range of productTeSys F
Motor starter typeDirect on-line contactor
Control circuit typeAC 40...400 Hz
Product or component typeContactor
Contactor coil voltage110 V AC standard
Coil voltage110 V AC 40...400 Hz
Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
Control circuit voltage limitsOperational 0.85...1.1 Uc 40...400 Hz 131 °F (55 °C)) Drop-out 0.3...0.5 Uc 40...400 Hz 131 °F (55 °C))
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current4200 A 104 °F (40 °C) - 10 s 3200 A 104 °F (40 °C) - 30 s 2400 A 104 °F (40 °C) - 1 min 1500 A 104 °F (40 °C) - 3 min 1200 A 104 °F (40 °C) - 10 min
Breaking capacity4000 A conforming to IEC 60947-4-1

All specifications

LC1F500F7 additional specifications
ParameterValue
[Ie] rated operational current700 A (at 500 A (at <131 °F (55 °C)) at <= 440 V AC AC-3
[Ith] conventional free air thermal current700 A (at 104 °F (40 °C))
Motor power250 kW at 380...400 V AC 50/60 Hz (AC-3) 280 kW at 415 V AC 50/60 Hz (AC-3) 295 kW at 440 V AC 50/60 Hz (AC-3) 355 kW at 500 V AC 50/60 Hz (AC-3) 335 kW at 660...690 V AC 50/60 Hz (AC-3) 335 kW at 1000 V AC 50/60 Hz (AC-3) 147 kW at 220...230 V AC 50/60 Hz (AC-3) 80 kW at 400 V AC 50/60 Hz (AC-4)
Motor power range250...500 kW 380...440 V 3 phase 110...220 kW 380...440 V 3 phase 110...220 kW 200...240 V 3 phase 250...500 kW 480...500 V 3 phase
Inrush power in1100 VA, 40...400 Hz 0.9 68 °F (20 °C))
Power dissipation per pole88 W AC-1 45 W AC-3
Power pole contact composition3 NO
Hold-in power consumption in18 VA, 40...400 Hz 0.9 68 °F (20 °C))
Poles description3P
Utilisation categoryAC-1 AC-3 AC-4
IP degree of protectionIP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106
Mounting supportPlate
Connections - terminalsControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 40 x 5 mm Power circuit lugs-ring terminals 2 0.4 in² (240 mm²) Power circuit bolted connection
Operating altitude9842.52 ft (3000 m) without derating
Depth9.1 in (232 mm)
Width9.2 in (233 mm)
Height9.4 in (238 mm)
Mechanical durability10 Mcycles
StandardsIEC 60947-4-1 JIS C8201-4-1 IEC 60947-1 EN 60947-1 EN 60947-4-1
RangeTeSys
CategoryUS10I1222336
Operating time40...65 ms closing 100...170 ms opening
Heat dissipation18 W
Average impedance0.18 mOhm - Ith 700 A 50 Hz
Device short nameLC1F
Tightening torqueControl circuit 10.6 lbf.in (1.2 N.m) Power circuit 309.8 lbf.in (35 N.m)
Compatibility codeLC1F
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationResistive load Motor control
Associated fuse rating500 A aM at 800 A gG at <= 440 V
Maximum operating rate2400 cyc/h 131 °F (55 °C)
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C)
MPN
LC1F500F7