Skip to main content
Schneider Electric LC1F630P7

Schneider Electric LC1F630P7

MPNLC1F630P7
Obsolete

LC1F630P7 - CONTACTOR by SCHNEIDER ELECTRIC

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC1F630P7 key specifications
ParameterValue
Range of productTeSys F
Motor starter typeDirect on-line contactor
Control circuit typeAC at 40...400 Hz
Product or component typeContactor
Contactor coil voltage230 V AC standard
Coil voltage230 V AC 40...400 Hz
Voltage1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C
Control circuit voltage limitsOperational: 0.85...1.1 Uc 40...400 Hz (at 55 °C) Drop-out: 0.25...0.5 Uc 40...400 Hz (at 55 °C)
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current5050 A 40 °C - 10 s 4400 A 40 °C - 30 s 3400 A 40 °C - 1 min 2200 A 40 °C - 3 min 1600 A 40 °C - 10 min
Breaking capacity5040 A conforming to IEC 60947-4-1

All specifications

LC1F630P7 additional specifications
ParameterValue
[Ie] rated operational current1000 A (at 630 A (at <55 °C) at <= 440 V AC AC-3
[Ith] conventional free air thermal current1000 A (at 40 °C)
Motor power335 kW at 380...400 V AC 50/60 Hz (AC-3) 375 kW at 415 V AC 50/60 Hz (AC-3) 400 kW at 440 V AC 50/60 Hz (AC-3) 400 kW at 500 V AC 50/60 Hz (AC-3) 450 kW at 660...690 V AC 50/60 Hz (AC-3) 450 kW at 1000 V AC 50/60 Hz (AC-3) 200 kW at 220...230 V AC 50/60 Hz (AC-3) 100 kW at 400 V AC 50/60 Hz (AC-4)
Motor power range250...500 kW at 380...440 V 3 phases 110...220 kW at 200...240 V 3 phases 250...500 kW at 480...500 V 3 phases
Inrush power in1650 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Power dissipation per pole120 W AC-1 48 W AC-3
Power pole contact composition3 NO
Hold-in power consumption in22 VA, 40...400 Hz cos phi 0.9 (at 20 °C)
Poles description3P
Utilisation categoryAC-1 AC-3 AC-4
IP degree of protectionIP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106
Mounting supportPlate
Connections - terminalsControl circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: bar 2 cable(s) - busbar cross section: 60 x 5 mm Power circuit: bolted connection
Operating altitude3000 m without derating
Depth255 mm
Width309 mm
Height304 mm
Product weight18.6 kg
Mechanical durability5 Mcycles
StandardsEN 60947-4-1 IEC 60947-4-1 JIS C8201-4-1 IEC 60947-1 EN 60947-1
RangeTeSys
Operating time40...80 ms closing 100...200 ms opening
Heat dissipation20 W
Average impedance0.12 mOhm - Ith 1000 A 50 Hz
Device short nameLC1F
Tightening torqueControl circuit: 1.2 N.m Power circuit: 58 N.m
Compatibility codeLC1F
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationResistive load Motor control
Associated fuse rating1000 A gG at 630 A aM at <= 440 V
Maximum operating rate1200 cyc/h 55 °C
Ambient air temperature for storage-60...80 °C
Ambient air temperature for operation-5...55 °C
Permissible ambient air temperature around the device-40...70 °C
MPN