Skip to main content
Schneider Electric LC1G3304EHES207N — Contactors

TeSys Giga LC1G3304EHES207N Contactor, 160 kW at 400 V AC-3e

MPNLC1G3304EHES207N
Active

Schneider Electric TeSys Giga LC1G3304EHES207N, 4-pole contactor, 160 kW at 400 V AC-3e, 48-130 V AC/DC coil, plate mount.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1G3304EHES207N — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationPower switching Motor control
LC1G3304EHES207N — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5
LC1G3304EHES207N — Contacts & Poles
ParameterValue
Pole configuration4P
LC1G3304EHES207N — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Protective treatment / pollution degreeTH
LC1G3304EHES207N — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ
LC1G3304EHES207N — Mechanical
ParameterValue
Width140 mm
Height225 mm
Depth225 mm

Product details

The Schneider Electric LC1G3304EHES207N is a TeSys Giga 4-pole contactor rated for 160 kW at 400 V AC in AC-3e duty — that's the motor-switching rating that governs real-world pump, fan, and conveyor loads. It also carries AC-1 (resistive), AC-4 (plugging/inching), and DC-1/DC-3/DC-5 ratings, so it covers resistive heating banks and DC loads too. Drop-out threshold is 0.1 to 0.45 Uc, so it releases reliably on a sagging control bus.

Plate-mounted, not DIN-rail — the 225 mm depth and 140 mm width need a backplate or sub-panel. Power connections are bolted: bar up to 32 x 10 mm busbar, or lugs up to 185 mm². Tightening torque on the power terminals is 35 N·m — that's substantial; use a torque wrench. Mechanical durability is 8 million cycles. The maximum operating rate is 500 cycles/hour in AC-3/AC-3e duty, 300 in AC-1, 150 in AC-4. For safety circuits, the B10d value is 400,000 cycles at nominal load per EN/ISO 13849-1.

Certified to EN/IEC 60947-4-1 and -5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1 and -5-1, plus UL 60335-1 and UL 60335-2-40 Annex JJ for appliance applications. Overvoltage category III. Protective treatment TH (tropicalized).

Frequently asked questions

What are the key motor ratings for this contactor?

In AC-3e duty, it handles 160 kW at 400 V AC, 160 kW at 415 V, 200 kW at 500 V, and 220 kW at 690 V. In horsepower terms: 250 hp at 460/480 V 60 Hz and 300 hp at 575/600 V 60 Hz.

What control voltage does this contactor use?

The coil accepts 48-130 V AC 50/60 Hz or 48-130 V DC, with built-in peak limiting. Drop-out occurs between 0.1 and 0.45 Uc.

What compliance documentation is available for this part?

It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, and UL 60335-2-40 Annex JJ.

MPN
LC1G3304EHES207N