Motor ratings and utilisation categories
In AC-3e duty it switches 315 kW at 690 V AC 50/60 Hz, and 220 kW at 1000 V AC. At 400 V AC the rating is 200 kW. These figures cover the common industrial voltages for pump, fan, and compressor loads. The utilisation categories listed include AC-1 through AC-8b plus DC-1, DC-3, and DC-5, so the contactor handles resistive heating, motor starting, and DC switching without derating concerns.
Certified to EN/IEC 60947-4-1 and EN/IEC 60947-5-1, plus UL 60947-4-1 and CSA C22.2 No 60947-4-1. Also carries JIS C8201-4-1 and JIS C8201-5-1 for Japanese markets. Overvoltage category III. The front face with shrouds achieves IP2X per IEC 60529 and VDE 0106.
Listed as current lifecycle stage. No official successor has been published. For BOM freeze or PCN watch, the compliance documentation set includes the standards listed above; RoHS and REACH declarations are available on request with the RFQ.
Mechanical and electrical endurance
Rated for 8 Mcycles mechanical durability. Maximum operating rate is 600 cycles/hour in AC-3 and AC-3e, 300 cycles/hour in AC-1, and 150 cycles/hour in AC-4. Inrush power at DC is 350 W.
Connection and mounting
Power circuit connections accept bar or busbar cross-section up to 32 x 10 mm, or lugs-ring terminals for 185 mm² cable. Tightening torque for power connections is 35 N.m. Mounting is plate-mount with a connection pitch of 45 mm. The dark grey housing measures 226 mm deep, 140 mm wide, and 225 mm high.