Skip to main content
Schneider Electric LC1G6304LSEN — Contactors

Schneider Electric LC1G6304LSEN TeSys Giga Contactor, 630 A,

MPNLC1G6304LSEN
Active

Schneider Electric TeSys Giga LC1G6304LSEN, 4-pole contactor, 630 A AC-3, 200-500 V AC/DC coil, dark grey.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1G6304LSEN — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationPower switching
LC1G6304LSEN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5
LC1G6304LSEN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1G6304LSEN — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Protective treatment / pollution degreeTH
LC1G6304LSEN — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ
LC1G6304LSEN — Mechanical
ParameterValue
Width11.06 in (281 mm)
Height11.2 in (284 mm)
Depth10.5 in (266 mm)

Product details

The LC1G6304LSEN is a 4-pole TeSys Giga contactor rated for 630 A in AC-3 duty, with a 200-500 V AC/DC coil. The coil uses built-in bidirectional peak limiting, so you don't need external suppression. Rated insulation voltage is 1000 V, and the contactor carries a making capacity of 7220 A at 440 V and a breaking capacity of 5550 A at 440 V — that's the short-circuit capability when coordinating with upstream protection.

The utilisation categories cover AC-3, AC-3e, AC-1, AC-5a, AC-5b, AC-6a, AC-6b, DC-1, DC-3, and DC-5. For resistive loads (AC-1), the thermal current Ith is 1050 A per pole. The contactor is rated for vibrations up to 4 gn when closed and shocks up to 15 gn — figures that matter on conveyors or mobile equipment. Power circuit terminals accept busbars up to 52 x 20 mm or ring lugs up to 185 mm². Control circuit uses push-in terminals for 0.2-2.5 mm² wire. The connection pitch is 70 mm, and tightening torque is 58 N·m on the power terminals.

Safety reliability data is available: B10d = 100,000 cycles at nominal load and 1,800,000 cycles at mechanical load per EN/ISO 13849-1. The auxiliary contact block is 1 NO + 1 NC built-in.

Sourcing posture

This is an active catalog item in the TeSys Giga range. No direct replacement needed; it's the current-generation part.

Frequently asked questions

What are the key ratings for this contactor?

630 A in AC-3 duty, 200-500 V AC/DC coil, 1000 V rated insulation voltage, 7220 A making capacity at 440 V, 5550 A breaking capacity at 440 V.

What compliance documentation does Schneider provide?

The contactor is certified to EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and UL 60335-1/-2-40. RoHS/REACH declarations are standard with the brand.

What is the physical size and color?

Dark grey enclosure. Dimensions: 11.2 in (284 mm) height, 11.06 in (281 mm) width, 10.5 in (266 mm) depth.

MPN