Skip to main content
Schneider Electric LC1G630EHES207N — Contactors

Schneider TeSys Giga LC1G630EHES207N Contactor, 630 A AC-3e,

MPNLC1G630EHES207N
Active

Schneider Electric TeSys Giga, LC1G630EHES207N, 3-pole contactor, 630 A AC-3e, 48-130 V AC/DC coil, 315 kW at 400 V.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026

Specifications

LC1G630EHES207N — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationPower switching Motor control
LC1G630EHES207N — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-1 AC-3 AC-3e AC-4 AC-5a AC-5b AC-6a AC-6b AC-8b AC-8a DC-1 DC-3 DC-5
LC1G630EHES207N — Contacts & Poles
ParameterValue
Pole configuration3P
LC1G630EHES207N — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds conforming to IEC 60529 IP2X front face with shrouds conforming to VDE 0106
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Protective treatment / pollution degreeTH
LC1G630EHES207N — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-1 UL 60335-2-40:Annex JJ
LC1G630EHES207N — Mechanical
ParameterValue
Width211 mm
Height284 mm
Depth266 mm

Product details

The LC1G630EHES207N is a 3-pole TeSys Giga contactor rated for 630 A in AC-3e duty. The AC-3e category (enhanced AC-3 per IEC 60947-4-1) means it is tested for the higher electrical endurance demanded by modern variable-speed drive inputs and frequent motor starts. The control circuit accepts 48-130 V AC/DC with built-in bidirectional peak limiting, so you do not need an external varistor or RC snubber across the coil. Drop-out is guaranteed between 0.1 and 0.45 Uc below 60 °C — useful to know if your control supply is shared with PLC outputs that sag during inrush. Mechanical durability is rated at 5 million cycles, and the B10d safety reliability figure is 100,000 cycles at nominal load per EN/ISO 13849-1. That puts it in the range for safety circuits where the contactor is part of a monitored stop chain, not just general power switching.

This contactor class sits inside motor control centres and large panel builds for pumps, conveyors, compressors, and HVAC fans. The plate-mount format and 70 mm connection pitch suit bolted busbar systems typical in 600+ A switchgear. The IP2X front face with shrouds meets touch-safe requirements per IEC 60529 and VDE 0106.

Integration notes

Mounting is plate-only — no DIN rail clip for this frame. Tightening torque for the power connections is 58 N·m. The 266 mm depth and 284 mm height need to be checked against enclosure gland-plate clearance and busbar rise. Power dissipation per pole is 70 W at AC-1 (Ith 1050 A) and 26 W at AC-3 (Ith 630 A). That heat has to be factored into panel ventilation — at full AC-3 load the three poles together dump 78 W into the enclosure.

Frequently asked questions

What are the key motor power ratings?

At 400 V AC 50/60 Hz in AC-3e duty it switches 315 kW. At 460/480 V 60 Hz the motor power is 600 hp. Full ratings across AC-3, AC-3e, and AC-4 categories are listed for voltages from 230 V to 1000 V.

What standards does this contactor comply with?

It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and JIS C8201-5-1, plus the appliance standards IEC 60335-1 Clause 30.2 and UL 60335-1.

What is the control voltage range?

The coil accepts 48-130 V AC 50/60 Hz and 48-130 V DC. Built-in bidirectional peak limiting handles coil suppression internally.

MPN