Skip to main content
Schneider Electric LC1G8004LSEN — Contactors

Schneider TeSys Giga LC1G8004LSEN Contactor, 4P, AC/DC Coil

MPNLC1G8004LSEN
Active

Schneider Electric TeSys Giga LC1G8004LSEN, 4-pole contactor, 800 A rated, coil 200...500 V AC/DC, plate mount, dark grey.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC1G8004LSEN — Identification
ParameterValue
Product / component typeContactor
Series / rangeTeSys
ApplicationPower switching
LC1G8004LSEN — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)<= 460 V DC
Utilisation categoryAC-3 AC-3e AC-1 AC-5a AC-5b AC-6a AC-6b DC-1 DC-3 DC-5
LC1G8004LSEN — Contacts & Poles
ParameterValue
Pole configuration4P
LC1G8004LSEN — Environmental
ParameterValue
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mechanical robustnessVibrations 5...300 Hz 2 gn contactor open Vibrations 5...300 Hz 4 gn contactor closed Shocks 10 gn 11 ms contactor open Shocks 15 gn 11 ms contactor closed
Protective treatment / pollution degreeTH
LC1G8004LSEN — Approvals
ParameterValue
StandardsEN/IEC 60947-4-1 EN/IEC 60947-5-1 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 JIS C8201-5-1 UL 60335-1 UL 60335-2-40:Annex JJ
LC1G8004LSEN — Mechanical
ParameterValue
Width11.06 in (281 mm)
Height11.2 in (284 mm)
Depth10.5 in (266 mm)

Product details

Utilisation categories cover AC-3 (squirrel-cage motor starting), AC-3e (high-efficiency motor starting), AC-1 (resistive loads), plus DC-1/DC-3/DC-5 for DC switching. The AC-3 rating is the one that governs most motor applications — this contactor is sized for 800 A in AC-3 duty, so it handles a 400–500 kW motor at 400 V without derating. Power dissipation per pole sits at 70 W in AC-1 at 1050 A and 42 W in AC-3 at 800 A. Associated fuse ratings are 800 A aM or 1250 A gG — the aM curve protects against motor start surges while the gG curve covers general fault clearing. For UL installations, a Type L fuse at ≤600 V is listed. Mechanical durability is 5 million cycles, with maximum operating rates of 600 cycles/hour in AC-3 and 300 cycles/hour in AC-1. That suits high-speed material handling or conveyor applications where the contactor cycles frequently.

Mounting and connection

Plate-mounted only (no DIN-rail option on this frame). The power terminals accept busbars up to 52 x 20 mm or ring lugs for 185 mm² cable. Tightening torque is 58 N·m on the power connections — a torque wrench is expected. Dimensions: 11.2 in (284 mm) high, 11.06 in (281 mm) wide, 10.5 in (266 mm) deep. The 70 mm connection pitch between poles matches the TeSys Giga busbar system. IP2X protection on the front face with shrouds installed.

The protective treatment (TH) indicates the contactor is tropicalized for high-humidity environments — a detail worth noting if the panel sits in an unconditioned plant area.

Frequently asked questions

What compliance certifications does this contactor carry?

It is certified to EN/IEC 60947-4-1, EN/IEC 60947-5-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, JIS C8201-5-1, UL 60335-1, and UL 60335-2-40:Annex JJ.

What is the coil voltage range and type?

The control circuit voltage is 200...500 V AC 50/60 Hz or 200...500 V DC. The coil includes built-in bidirectional peak limiting.

What are the main utilisation categories for this contactor?

It covers AC-3, AC-3e, AC-1, AC-5a, AC-5b, AC-6a, AC-6b, DC-1, DC-3, and DC-5. For motor loads, AC-3 is the primary rating.

MPN
LC1G8004LSEN