Skip to main content
Schneider Electric LC1K06105M7

Schneider Electric LC1K06105M7

MPNLC1K06105M7
Obsolete

TeSys K contactor, 3P, AC-3 <= 440 V 6 A, 1 NO aux., 220...230 V AC coil

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1K06105M7 key specifications
ParameterValue
Auxiliary contacts typeInstantaneous 1 NO
Product or component typeContactor
Minimum switching voltage17 V for signalling circuit
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at Drop-out: >= 0.20 Uc (at <122 °F (50 °C))
[Ue] rated operational voltagePower circuit Signalling circuit 10 MOhm for signalling circuit
Minimum switching current5 mA for signalling circuit
Inrush power in30 VA (at 68 °F (20 °C))
Power pole contact composition3 NO
Hold-in power consumption in4.5 VA (at 68 °F (20 °C))
Signalling circuit frequency<= 400 Hz
Poles description3P
Utilisation categoryAC-3 AC-3e AC-4

All specifications

LC1K06105M7 additional specifications
ParameterValue
IP degree of protectionIP2X VDE 0106
Mounting supportPrinted circuit boards
Connections - terminalssolder pins 0.001 in (0.035 mm))
Operating altitude6561.68 ft (2000 m) without derating
Depth2.2 in (57 mm)
Width1.8 in (45 mm)
Height2.3 in (58 mm)
Electrical durability1.3 Mcycles 6 A AC-3 1.3 Mcycles 6 A AC-3e 0.05 Mcycles 36 A AC-4 <= 440 V
Mechanical durability10 Mcycles
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ
RangeTeSys
Category22326-CTR,K-LINE,AC,OPEN,NONREV
Operating time10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing
Coil technologyWithout built-in suppressor module
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Heat dissipation1.3 W
Device short nameLC1K
Device applicationControl
Non overlap distance0.02 in (0.5 mm)
Protective treatmentTC IEC 60068 TC DIN 50016
Contactor applicationMotor control
Mechanical robustnessShocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Maximum operating rate3600 cyc/h
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Ambient air temperature for storage-58...176 °F (-50...80 °C)
MPN
LC1K06105M7