Skip to main content
Schneider Electric LC1K12013F7

Schneider Electric LC1K12013F7

MPNLC1K12013F7
Active

LC1K12013F7 - TESYS K by SCHNEIDER ELECTRIC

$33.69Ref. price · indicative, final on quote
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC1K12013F7 key specifications
ParameterValue
Auxiliary contacts typetype instantaneous 1 NC
Product or component typeContactor
Minimum switching voltage17 V for signalling circuit
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at Drop-out: >= 0.20 Uc (at <50 °C)
[Ue] rated operational voltagePower circuit: Signalling circuit: 10 MOhm for signalling circuit
Minimum switching current5 mA for signalling circuit
Inrush power in30 VA (at 20 °C)
Power pole contact composition3 NO
Hold-in power consumption in4.5 VA (at 20 °C)
Signalling circuit frequency<= 400 Hz
Poles description3P
Utilisation categoryAC-3 AC-3e AC-1 AC-4

All specifications

LC1K12013F7 additional specifications
ParameterValue
Connections - terminalsSpring terminals 1 cable(s) 0.75...1.5 mm²solid Spring terminals 1 cable(s) 0.75...1.5 mm²flexible without cable end Spring terminals 2 cable(s) 0.75...1.5 mm²flexible without cable end
Operating altitude2000 m without derating
Depth57 mm
Width45 mm
Height58 mm
Electrical durability1.3 Mcycles 12 A AC-3 at Ue 1.3 Mcycles 12 A AC-3e at Ue 0.3 Mcycles 20 A AC-1 at Ue 0.02 Mcycles 72 A AC-4 at Ue <= 440 V
Mechanical durability10 Mcycles
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1 IEC 60335-1:Clause 30.2 IEC 60335-2-40:Annex JJ UL 60335-2-40:Annex JJ
RangeTeSys
Operating time10...20 ms coil de-energisation and NO opening 10...20 ms coil energisation and NO closing
Coil technologyWithout built-in suppressor module
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Heat dissipation1.3 W
Device short nameLC1K
Device applicationControl
Non overlap distance0.5 mm
Protective treatmentTC conforming to IEC 60068 TC conforming to DIN 50016
Contactor applicationMotor control Resistive load
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Maximum operating rate3600 cyc/h
Safety reliability levelB10d = 1369863 cycles contactor with nominal load conforming to EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load conforming to EN/ISO 13849-1
MPN
LC1K12013F7