Skip to main content
Schneider Electric LC2D80004N7

Schneider Electric LC2D80004N7

MPNLC2D80004N7
Obsolete

TeSys D changeover contactor - 4P(4 NO) - AC-1 - <= 440 V 125 A - 415 V AC coil

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

LC2D80004N7 key specifications
ParameterValue
Interlocking typeMechanical
Control circuit typeAC 50/60 Hz
Product or component typeChangeover contactor
Climatic withstandIACS E10
Coil voltage415 V AC 50/60 Hz
VoltagePower circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1
Control circuit voltage limits0.3...0.6 Uc (-40...158 °F (-40...70 °C)):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...131 °F (-40...55 °C)):operational AC 50 Hz 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational AC 60 Hz 1...1.1 Uc (131...158 °F (55...70 °C)):operational AC 50/60 Hz
[Ue] rated operational voltagePower circuit Power circuit <= 300 V DC
[Uimp] rated impulse withstand voltage8 kV IEC 60947
[Icw] rated short-time withstand current135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit 640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit
Breaking capacity1100 A at 440 V for power circuit conforming to IEC 60947
[Ie] rated operational current125 A (at 80 A (at 80 A (at 55 A (at <140 °F (60 °C)) at <= 400 V AC AC-4 for power circuit

All specifications

LC2D80004N7 additional specifications
ParameterValue
[Ith] conventional free air thermal current125 A (at 140 °F (60 °C)) for power circuit
Inrush power in245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C))
Power dissipation per pole12.5 W AC-1
Power pole contact composition4 NO
Hold-in power consumption in26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) 26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C))
Poles description4P
Utilisation categoryAC-1 AC-3 AC-3e AC-4
IP degree of protectionIP20 front face IEC 60529
Mounting supportPlate Rail
Connections - terminalsControl circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid Control circuit screw clamp terminals 1 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Power circuit connector 1 0.006...0.08 in² (4...50 mm²)flexible without cable end Power circuit connector 2 0.006...0.04 in² (4...25 mm²)flexible without cable end Power circuit connector 1 0.006...0.08 in² (4...50 mm²)flexible with cable end Power circuit connector 2 0.006...0.02 in² (4...16 mm²)flexible with cable end Power circuit connector 1 0.006...0.08 in² (4...50 mm²)solid Power circuit connector 2 0.006...0.04 in² (4...25 mm²)solid
Pollution degree3
Operating altitude0...9842.52 ft (0...3000 m)
Depth6.2 in (158 mm)
Width8.1 in (207 mm)
Height5 in (127 mm)
Electrical durability0.8 Mcycles 125 A AC-1 <= 440 V
Mechanical durability4 Mcycles
StandardsCSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508
RangeTeSys
Category22359-CTR,TESYS D,OPEN,80-150A AC&DC
Front coverWithout
Operating time20...35 ms closing 6...20 ms opening
Coil technologyWithout built-in suppressor module
Fire resistance1562 °F (850 °C) IEC 60695-2-1
Flame retardanceV1 conforming to UL 94
Heat dissipation6...10 W 50/60 Hz
Average impedance0.8 mOhm - Ith 125 A 50 Hz for power circuit
Device short nameLC2D
Tightening torqueControl circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm)
Device presentationPreassembled, with prewired power connections
Overvoltage categoryIII
Protective treatmentTH IEC 60068-2-30
Contactor applicationResistive load
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Shocks contactor open8 Gn for 11 ms Vibrations contactor closed3 Gn, 5...300 Hz Shocks contactor closed10 Gn for 11 ms
Associated fuse rating200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit
Maximum operating rate3600 cyc/h 140 °F (60 °C)
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity1100 A at 440 V for power circuit conforming to IEC 60947
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation-40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating
MPN