Schneider Electric LC2D80004V7
MPNLC2D80004V7
Obsolete
Changeover contactor, TeSys Deca, 4P(4 NO), AC-1, <= 440 V 125 A - 400 V AC coil
StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →Specifications
| Parameter | Value |
|---|---|
| Interlocking type | Mechanical |
| Control circuit type | AC 50/60 Hz |
| Product or component type | Changeover contactor |
| Climatic withstand | IACS E10 |
| Coil voltage | 400 V AC 50/60 Hz |
| Voltage | Power circuit 600 V CSA Power circuit 600 V UL Power circuit 1000 V IEC 60947-4-1 |
| Control circuit voltage limits | 0.3...0.6 Uc (-40...158 °F (-40...70 °C)):drop-out AC 50/60 Hz 0.8...1.1 Uc (-40...131 °F (-40...55 °C)):operational AC 50 Hz 0.85...1.1 Uc (-40...131 °F (-40...55 °C)):operational AC 60 Hz 1...1.1 Uc (131...158 °F (55...70 °C)):operational AC 50/60 Hz |
| [Ue] rated operational voltage | Power circuit Power circuit <= 300 V DC |
| [Uimp] rated impulse withstand voltage | 8 kV IEC 60947 |
| [Icw] rated short-time withstand current | 135 A 104 °F (40 °C) - 10 min for power circuit 320 A 104 °F (40 °C) - 1 min for power circuit 640 A 104 °F (40 °C) - 10 s for power circuit 990 A 104 °F (40 °C) - 1 s for power circuit |
| Breaking capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| [Ie] rated operational current | 125 A (at 80 A (at 80 A (at 55 A (at <140 °F (60 °C)) at <= 400 V AC AC-4 for power circuit |
All specifications
| Parameter | Value |
|---|---|
| [Ith] conventional free air thermal current | 125 A (at 140 °F (60 °C)) for power circuit |
| Inrush power in | 245 VA 60 Hz cos phi 0.75 (at 68 °F (20 °C)) 245 VA 50 Hz cos phi 0.75 (at 68 °F (20 °C)) |
| Power dissipation per pole | 12.5 W AC-1 |
| Power pole contact composition | 4 NO |
| Hold-in power consumption in | 26 VA 60 Hz cos phi 0.3 (at 68 °F (20 °C)) 26 VA 50 Hz cos phi 0.3 (at 68 °F (20 °C)) |
| Poles description | 4P |
| Utilisation category | AC-1 AC-3 AC-3e AC-4 |
| IP degree of protection | IP20 front face IEC 60529 |
| Mounting support | Rail Plate |
| Connections - terminals | Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid Control circuit screw clamp terminals 1 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Power circuit connector 1 0.006...0.08 in² (4...50 mm²)flexible without cable end Power circuit connector 2 0.006...0.04 in² (4...25 mm²)flexible without cable end Power circuit connector 1 0.006...0.08 in² (4...50 mm²)flexible with cable end Power circuit connector 2 0.006...0.02 in² (4...16 mm²)flexible with cable end Power circuit connector 1 0.006...0.08 in² (4...50 mm²)solid Power circuit connector 2 0.006...0.04 in² (4...25 mm²)solid |
| Pollution degree | 3 |
| Operating altitude | 0...9842.52 ft (0...3000 m) |
| Depth | 6.2 in (158 mm) |
| Width | 8.1 in (207 mm) |
| Height | 5 in (127 mm) |
| Electrical durability | 0.8 Mcycles 125 A AC-1 <= 440 V |
| Mechanical durability | 4 Mcycles |
| Standards | CSA C22.2 No 14 EN 60947-4-1 EN 60947-5-1 IEC 60947-4-1 IEC 60947-5-1 UL 508 |
| Range | TeSys |
| Category | 22359-CTR,TESYS D,OPEN,80-150A AC&DC |
| Front cover | Without |
| Operating time | 20...35 ms closing 6...20 ms opening |
| Coil technology | Without built-in suppressor module |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Flame retardance | V1 conforming to UL 94 |
| Heat dissipation | 6...10 W 50/60 Hz |
| Average impedance | 0.8 mOhm - Ith 125 A 50 Hz for power circuit |
| Device short name | LC2D |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals flat Ø 6 mm Control circuit 10.6 lbf.in (1.2 N.m) screw clamp terminals Philips No 2 Power circuit 106.2 lbf.in (12 N.m) connector flat Ø 6 to Ø 8 mm Power circuit 106.2 lbf.in (12 N.m) connector hexagonal 0.2 in (4 mm) |
| Device presentation | Preassembled, with prewired power connections |
| Overvoltage category | III |
| Protective treatment | TH IEC 60068-2-30 |
| Contactor application | Resistive load |
| Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz Shocks contactor open8 Gn for 11 ms Vibrations contactor closed3 Gn, 5...300 Hz Shocks contactor closed10 Gn for 11 ms |
| Associated fuse rating | 200 A gG at 160 A gG at <= 690 V coordination type 2 for power circuit |
| Maximum operating rate | 3600 cyc/h 140 °F (60 °C) |
| Safety reliability level | B10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1 |
| Irms rated making capacity | 1100 A at 440 V for power circuit conforming to IEC 60947 |
| Ambient air temperature for storage | -76...176 °F (-60...80 °C) |
| Ambient air temperature for operation | -40...140 °F (-40...60 °C) 140...158 °F (60...70 °C) with derating |
MPN
LC2D80004V7