Skip to main content
Schneider Electric LC2F1154

Schneider Electric LC2F1154

MPNLC2F1154
Obsolete

TeSys F changeover contactor - 4P(4 NO) AC-1 <= 440 V 200 A - without coil

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2F1154 key specifications
ParameterValue
Interlocking typeMechanical
Product or component typeChangeover contactor
Voltage1000 V IEC 60947-4-1 1500 V VDE 0110 group C
[Ue] rated operational voltage<= 460 V DC
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current1100 A 104 °F (40 °C) - 10 s 640 A 104 °F (40 °C) - 30 s 520 A 104 °F (40 °C) - 1 min 400 A 104 °F (40 °C) - 3 min 320 A 104 °F (40 °C) - 10 min
Breaking capacity920 A conforming to IEC 60947-4-1
[Ie] rated operational current200 A (at <104 °F (40 °C)) at <= 440 V AC AC-1
[Ith] conventional free air thermal current200 A (at 104 °F (40 °C))
Power dissipation per pole15 W AC-1
Power pole contact composition4 NO
Poles description4P

All specifications

LC2F1154 additional specifications
ParameterValue
Utilisation categoryAC-1
IP degree of protectionIP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106
Mounting supportPlate
Connections - terminalsPower circuit connector 1 0.1 in² (95 mm²) Power circuit lugs-ring terminals 1 0.1 in² (95 mm²) Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit bar 2 20 x 3 mm
Operating altitude9842.52 ft (3000 m) without derating
Depth6.7 in (171 mm)
Width16.5 in (419 mm)
Height6.4 in (162 mm)
StandardsEN 60947-1 IEC 60947-4-1 JIS C8201-4-1 EN 60947-4-1 IEC 60947-1
RangeTeSys
Category18401-WORLD SERVICE PARTS(CTR ACCESS)
Fire resistance1562 °F (850 °C) IEC 60695-2-1
Average impedance0.37 mOhm - Ith 200 A 50 Hz
Device short nameLC2F
Tightening torquePower circuit 88.5 lbf.in (10 N.m) Control circuit 10.6 lbf.in (1.2 N.m)
Device presentationPreassembled with reversing power busbar
Overvoltage categoryIII
Protective treatmentTH
Contactor applicationResistive load
Mechanical robustnessVibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms
Associated fuse rating125 A aM at 200 A gG at <= 440 V
Irms rated making capacity1150 A AC conforming to IEC 60947-4-1
Auxiliary contact composition1 NO
Ambient air temperature for storage-76...176 °F (-60...80 °C)
Ambient air temperature for operation23...131 °F (-5...55 °C)
Permissible ambient air temperature around the device-40...158 °F (-40...70 °C)
MPN