Schneider Electric LC2F150
MPNLC2F150
Obsolete
TeSys F reversing contactor - 3P(3 NO) AC-3 <= 440 V 150 A - without coil
$657.23 – $1,345.54Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Interlocking type | Mechanical |
| Product or component type | Reversing contactor |
| Voltage | 1000 V IEC 60947-4-1 1500 V VDE 0110 group C |
| [Ue] rated operational voltage | <= 460 V DC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Icw] rated short-time withstand current | 1200 A 104 °F (40 °C) - 10 s 700 A 104 °F (40 °C) - 30 s 600 A 104 °F (40 °C) - 1 min 450 A 104 °F (40 °C) - 3 min 350 A 104 °F (40 °C) - 10 min |
| Breaking capacity | 1200 A conforming to IEC 60947-4-1 |
| [Ie] rated operational current | 250 A (at 150 A (at <131 °F (55 °C)) at <= 440 V AC AC-3 |
| [Ith] conventional free air thermal current | 250 A (at 104 °F (40 °C)) |
| Motor power | 65 kW 1000 V AC 50/60 Hz 75 kW 380...400 V AC 50/60 Hz 80 kW 415 V AC 50/60 Hz 80 kW 440 V AC 50/60 Hz 90 kW 500 V AC 50/60 Hz 40 kW 220...240 V AC 50/60 Hz 100 kW 660...690 V AC 50/60 Hz |
| Power dissipation per pole | 8 W AC-3 |
| Power pole contact composition | 3 NO |
All specifications
| Parameter | Value |
|---|---|
| Poles description | 3P |
| Utilisation category | AC-3 AC-1 |
| IP degree of protection | IP2X front face with shrouds IEC 60529 IP2X front face with shrouds VDE 0106 |
| Mounting support | Plate |
| Connections - terminals | Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit connector 1 0.2 in² (120 mm²) Power circuit lugs-ring terminals 1 0.2 in² (120 mm²) Power circuit bar 2 25 x 3 mm |
| Operating altitude | 9842.52 ft (3000 m) without derating |
| Depth | 6.7 in (171 mm) |
| Width | 13.6 in (345 mm) |
| Height | 6.7 in (170 mm) |
| Standards | EN 60947-4-1 JIS C8201-4-1 EN 60947-1 IEC 60947-4-1 IEC 60947-1 |
| Range | TeSys |
| Category | US10I1222337 |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Average impedance | 0.35 mOhm - Ith 250 A 50 Hz |
| Device short name | LC2F |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 159.3 lbf.in (18 N.m) |
| Device presentation | Preassembled with reversing power busbar |
| Overvoltage category | III |
| Protective treatment | TH |
| Contactor application | Resistive load Motor control |
| Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz Vibrations contactor closed6 Gn, 5...300 Hz Shocks contactor open9 Gn for 11 ms Shocks contactor closed15 Gn for 11 ms |
| Associated fuse rating | 160 A aM at 250 A gG at <= 440 V |
| Irms rated making capacity | 1500 A AC conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO |
| Ambient air temperature for storage | -76...176 °F (-60...80 °C) |
| Ambient air temperature for operation | 23...131 °F (-5...55 °C) |
| Permissible ambient air temperature around the device | -40...158 °F (-40...70 °C) |
MPN