Schneider Electric LC2F225M7
MPNLC2F225M7
Obsolete
TeSys F reversing contactor - 3P(3 NO) AC-3 <= 440 V 225 A 220 V AC 40...400 Hz
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Interlocking type | Mechanical |
| Control circuit type | AC at 40...400 Hz |
| Product or component type | Reversing contactor |
| Coil voltage | 220 V AC 40...400 Hz |
| Voltage | 1000 V conforming to IEC 60947-4-1 1500 V conforming to VDE 0110 group C |
| Control circuit voltage limits | Operational: 0.85...1.1 Uc at 50/60 Hz (at Drop-out: 0.2...0.55 Uc at 50/60 Hz (at <55 °C) |
| [Ue] rated operational voltage | <= 460 V DC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Icw] rated short-time withstand current | 1800 A 40 °C - 10 s 1000 A 40 °C - 30 s 850 A 40 °C - 1 min 560 A 40 °C - 3 min 440 A 40 °C - 10 min |
| Breaking capacity | 1800 A conforming to IEC 60947-4-1 |
| [Ie] rated operational current | 225 A (at 315 A (at <40 °C) at <= 440 V AC AC-1 |
| [Ith] conventional free air thermal current | 315 A (at 40 °C) |
All specifications
| Parameter | Value |
|---|---|
| Motor power | 100 kW at 1000 V AC 50/60 Hz 110 kW at 380...400 V AC 50/60 Hz 110 kW at 415 V AC 50/60 Hz 110 kW at 440 V AC 50/60 Hz 129 kW at 500 V AC 50/60 Hz 63 kW at 220...240 V AC 50/60 Hz 129 kW at 660...690 V AC 50/60 Hz |
| Inrush power in | 805 VA 50 Hz cos phi 0.3 (at 20 °C) 970 VA 60 Hz cos phi 0.3 (at 20 °C) |
| Power dissipation per pole | 16 W AC-3 |
| Power pole contact composition | 3 NO |
| Hold-in power consumption in | 55 VA 50 Hz cos phi 0.3 (at 20 °C) 66 VA 60 Hz cos phi 0.3 (at 20 °C) |
| Poles description | 3P |
| Utilisation category | AC-1 AC-3 |
| IP degree of protection | IP20 front face with shrouds conforming to IEC 60529 IP20 front face with shrouds conforming to VDE 0106 |
| Mounting support | Plate |
| Connections - terminals | Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²flexible without cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²flexible with cable end Control circuit: screw clamp terminals 2 cable(s) 1...2.5 mm²flexible with cable end Control circuit: screw clamp terminals 1 cable(s) 1...4 mm²solid without cable end Control circuit: screw clamp terminals 2 cable(s) 1...4 mm²solid without cable end Power circuit: lugs-ring terminals 1 cable(s) 185 mm² Power circuit: connector 1 cable(s) 185 mm² Power circuit: bar 2 cable(s) - busbar cross section: 32 x 4 mm |
| Operating altitude | 3000 m without derating |
| Depth | 181 mm |
| Width | 357 mm |
| Height | 197 mm |
| Mechanical durability | 10 Mcycles |
| Standards | IEC 60947-1 EN 60947-1 EN 60947-4-1 IEC 60947-4-1 JIS C8201-4-1 |
| Range | TeSys |
| Operating time | 20...35 ms closing 7...15 ms opening |
| Heat dissipation | 18...24 W |
| Average impedance | 0.32 mOhm - Ith 315 A 50 Hz |
| Device short name | LC2F |
| Tightening torque | Control circuit: 1.2 N.m Power circuit: 35 N.m |
| Device presentation | Preassembled with reversing power busbar |
| Overvoltage category | III |
| Protective treatment | TH |
| Contactor application | Motor control Resistive load |
| Mechanical robustness | Vibrations contactor open: 2 Gn, 5...300 Hz Shocks contactor closed: 15 Gn for 11 ms Vibrations contactor closed: 5 Gn, 5...300 Hz Shocks contactor open: 7 Gn for 11 ms |
| Associated fuse rating | 315 A gG at 250 A aM at <= 440 V |
| Maximum operating rate | 2400 cyc/h 55 °C |
| Irms rated making capacity | 2250 A AC conforming to IEC 60947-4-1 |
| Ambient air temperature for storage | -60...80 °C |
| Ambient air temperature for operation | -5...55 °C |
| Permissible ambient air temperature around the device | -40...70 °C |
MPN