Schneider Electric LC2F2654
MPNLC2F2654
Obsolete
TeSys F changeover contactor - 4P(4 NO) AC-1 <= 440 V 350 A - without coil
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026
Specifications
| Parameter | Value |
|---|---|
| Interlocking type | Mechanical |
| Product or component type | Changeover contactor |
| Voltage | 1000 V IEC 60947-4-1 1500 V VDE 0110 group C |
| [Ue] rated operational voltage | <= 460 V DC |
| [Uimp] rated impulse withstand voltage | 8 kV |
| [Icw] rated short-time withstand current | 2200 A 104 °F (40 °C) - 10 s 1230 A 104 °F (40 °C) - 30 s 950 A 104 °F (40 °C) - 1 min 620 A 104 °F (40 °C) - 3 min 480 A 104 °F (40 °C) - 10 min |
| Breaking capacity | 2120 A conforming to IEC 60947-4-1 |
| [Ie] rated operational current | 350 A (at <104 °F (40 °C)) at <= 440 V AC AC-1 |
| [Ith] conventional free air thermal current | 350 A (at 104 °F (40 °C)) |
| Power dissipation per pole | 37 W AC-1 |
| Power pole contact composition | 4 NO |
| Poles description | 4P |
All specifications
| Parameter | Value |
|---|---|
| Utilisation category | AC-1 |
| IP degree of protection | IP20 front face with shrouds IEC 60529 IP20 front face with shrouds VDE 0106 |
| Mounting support | Plate |
| Connections - terminals | Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)flexible without cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)flexible with cable end Control circuit screw clamp terminals 2 0.002...0.004 in² (1...2.5 mm²)flexible with cable end Control circuit screw clamp terminals 1 0.002...0.006 in² (1...4 mm²)solid without cable end Control circuit screw clamp terminals 2 0.002...0.006 in² (1...4 mm²)solid without cable end Power circuit connector 1 0.4 in² (240 mm²) Power circuit lugs-ring terminals 1 0.4 in² (240 mm²) Power circuit bar 2 32 x 4 mm |
| Operating altitude | 9842.52 ft (3000 m) without derating |
| Depth | 8.4 in (213 mm) |
| Width | 20.5 in (521 mm) |
| Height | 8.0 in (203 mm) |
| Standards | EN 60947-4-1 IEC 60947-1 JIS C8201-4-1 EN 60947-1 IEC 60947-4-1 |
| Range | TeSys |
| Category | 18401-WORLD SERVICE PARTS(CTR ACCESS) |
| Fire resistance | 1562 °F (850 °C) IEC 60695-2-1 |
| Average impedance | 0.3 mOhm - Ith 350 A 50 Hz |
| Device short name | LC2F |
| Tightening torque | Control circuit 10.6 lbf.in (1.2 N.m) Power circuit 309.8 lbf.in (35 N.m) |
| Device presentation | Preassembled with reversing power busbar |
| Overvoltage category | III |
| Protective treatment | TH |
| Contactor application | Resistive load |
| Mechanical robustness | Vibrations contactor open2 Gn, 5...300 Hz Shocks contactor closed15 Gn for 11 ms Vibrations contactor closed5 Gn, 5...300 Hz Shocks contactor open6 Gn for 11 ms |
| Associated fuse rating | 315 A aM at 400 A gG at <= 440 V |
| Irms rated making capacity | 2650 A AC conforming to IEC 60947-4-1 |
| Auxiliary contact composition | 1 NO |
| Ambient air temperature for storage | -76...176 °F (-60...80 °C) |
| Ambient air temperature for operation | 23...131 °F (-5...55 °C) |
| Permissible ambient air temperature around the device | -40...158 °F (-40...70 °C) |
MPN
LC2F2654