Skip to main content
Schneider Electric LC2K06015R7 — Contactors

TeSys K LC2K06015R7 reversing contactor, 3P, AC-3 6 A at 440

MPNLC2K06015R7
Active

Schneider Electric TeSys K reversing contactor, LC2K06015R7, 3P, AC-3 <=440 V 6 A, 1 NC, 440 V AC coil, preassembled with reversing power busbar.

Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Aug 2026

Specifications

LC2K06015R7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K06015R7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K06015R7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K06015R7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K06015R7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Rated AC-3 <=440 V 6 A, it switches three-phase squirrel-cage motors up to that current in reversing duty. The 440 V AC coil matches standard European control voltages. AC-3 is the utilisation category for starting and stopping squirrel-cage motors under load — the 6 A rating at <=440 V is the current the contactor can break reliably during normal motor starts. AC-4 (also listed) covers inching and plugging, where the contactor interrupts locked-rotor current, so this part handles both reversing and jogging cycles without derating.

IP20 finger-safe terminals suit enclosed panel mounting, not open washdown areas. Preassembled with reversing power busbar means no separate busbar kit to order and no risk of wiring the interlock wrong in the field. The 1 NC auxiliary contact provides a positive feedback path for the control logic to confirm the contactor state.

Frequently asked questions

What are the key ratings for this reversing contactor?

3-pole, AC-3 <=440 V 6 A motor rating, 440 V AC coil, 1 NC auxiliary contact. IP20. Operating temperature -25 to 50 °C, no derating to 2000 m altitude.

What compliance documentation does Schneider Electric provide for LC2K06015R7?

Flame retardance V1 per UL 94, plus compliance with NF F 16-101 and NF F 16-102 (French railway standards). Protective treatment per IEC 60068 and DIN 50016 (tropical climate). Shock and vibration tested per IEC 60068-2-27 and IEC 60068-2-6.

What is the closest alternative to LC2K06015R7 in the TeSys K family?

Within the same TeSys K family, the single-direction contactor (e.g., LC1K0601) shares the same coil voltage and pole configuration but lacks the reversing busbar and mechanical interlock. For a reversing pair built from two singles, you would add a separate reversing busbar kit and external interlock — the LC2K06015R7 is the factory-assembled version that saves panel space and wiring time.

MPN
LC2K06015R7