TeSys K LC2K0601W7 reversing contactor, 3P, 6 A AC-3, 256 V

MPNLC2K0601W7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 <=440 V 6 A, 1 NC, 256 V AC coil, preassembled with reversing power busbar.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K0601W7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K0601W7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K0601W7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K0601W7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K0601W7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Rated for AC-3 and AC-4 utilization categories, it switches motor loads up to 6 A at 440 V AC — the AC-3 rating governs the motor starting current, while AC-4 covers plugging or inching duty where the contactor makes and breaks stalled-rotor current. The 256 V AC coil is the control voltage you need to supply; the contactor pulls in cleanly on that nominal and drops out reliably below the release threshold. Built into the TeSys K family, this reversing contactor is sized for control panels where direction reversal of a small motor (conveyor, fan, actuator) is required. The IP20 finger-safe enclosure meets VDE 0106, so it's suitable for enclosed panel environments where accidental contact with live parts must be prevented.

Frequently asked questions

What is the closest alternative to the LC2K0601W7 in the TeSys K family?

Within the TeSys K family, the closest peer would be a reversing contactor with the same pole configuration and coil voltage but a different auxiliary contact arrangement. The LC2K0601W7 carries 1 NC auxiliary; if you need 1 NO instead, the sibling with that contact configuration is the direct swap. Both share the same footprint, busbar, and AC-3 rating.

What is the depth of the LC2K0601W7?

The depth is 57 mm, with a width of 90 mm and height of 58 mm.

What compliance documentation is available for the LC2K0601W7?

The part carries flame retardance V1 per UL 94, plus compliance with NF F 16-101 and NF F 16-102 for railway fire-smoke. It is IP20 per VDE 0106. For RoHS, REACH, and full UL/IEC certification, the manufacturer's declaration pack is available through the standard documentation portal.

MPN