Schneider Electric LC2K06103U7 — Contactors

Schneider TeSys K LC2K06103U7 Reversing Contactor, 3P, 6A AC

MPNLC2K06103U7
Active

Schneider Electric TeSys K reversing contactor, LC2K06103U7, 3P, AC-3 <=440V 6A, 1 NO, 230-240VAC coil, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K06103U7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K06103U7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K06103U7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K06103U7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K06103U7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric TeSys K LC2K06103U7 is a 3-pole reversing contactor rated for motor control in AC-3 and AC-4 utilisation categories. The contactor ships preassembled with the reversing power busbar, so the mechanical interlock and main power wiring between the two contactor halves is already in place, saving panel build time.

The coil is 230-240 VAC, so it drops straight into a 240 V control transformer secondary without an extra buck-boost. Rated operational voltage on the power circuit is 690 V AC 50/60 Hz, giving headroom for 480 V or 600 V line applications, though the motor current rating must be derated above 440 V per the manufacturer's curve.

For higher ambient or altitude above 2000 m, derate the continuous current accordingly.

The contactor carries V1 flame retardance per UL 94 and meets NF F 16-101 / NF F 16-102 for railway fire-smoke-toxicity requirements. Protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance. Mechanical robustness is specified for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6, with the contactor withstanding 10-15 Gn shocks in the closed position and 4 Gn vibration at 5-300 Hz.

Frequently asked questions

What is the closest alternative to LC2K06103U7 in the TeSys K family?

Within the TeSys K reversing contactor range, the LC2K06103U7 is defined by its 6 A AC-3 rating and 230-240 VAC coil. The closest sibling would share the same frame and pole count but differ in coil voltage (e.g., 24 VAC or 110 VAC variants) or current rating (e.g., 9 A frame). The mechanical interlock and busbar assembly are common across the series, so swapping to a different coil voltage variant is a direct fit for the same panel layout.

What compliance documentation does Schneider provide for LC2K06103U7?

The contactor is UL 94 V1 rated for flame retardance and meets NF F 16-101/102 for railway fire safety. Protective treatment complies with IEC 60068 and DIN 50016. Shock and vibration testing follows IEC 60068-2-27 and IEC 60068-2-6. Standard Schneider declarations (CE, UKCA, EAC) apply per the TeSys K series documentation.

MPN
LC2K06103U7