Skip to main content
Schneider Electric LC2K09004B7

Schneider LC2K09004B7 TeSys K Reversing Contactor, 24V AC, 2

MPNLC2K09004B7
Obsolete

Schneider Electric TeSys K reversing contactor LC2K09004B7, 4-pole, 24 V AC 50/60 Hz coil, 20 A AC-1 resistive load, preassembled with reversing power busbar.

$36.83Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K09004B7 key specifications
ParameterValue
Interlocking typeMechanical
Control circuit typeAC 50/60 Hz
Product or component typeChangeover contactor
Coil voltage24 V AC 50/60 Hz
VoltagePower circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA C22.2 No 14
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at Drop-out: 0.2...0.75 Uc (at <122 °F (50 °C))
[Ue] rated operational voltagePower circuit 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current90 A 122 °F (50 °C) - 1 s for power circuit 85 A 122 °F (50 °C) - 5 s for power circuit 80 A 122 °F (50 °C) - 10 s for power circuit 60 A 122 °F (50 °C) - 30 s for power circuit 45 A 122 °F (50 °C) - 1 min for power circuit 40 A 122 °F (50 °C) - 3 min for power circuit 20 A 122 °F (50 °C) - >= 15 min for power circuit
Breaking capacity110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947
[Ie] rated operational current20 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current20 A (at 140 °F (60 °C)) for power circuit

All specifications

LC2K09004B7 additional specifications
ParameterValue
Inrush power in30 VA (at 68 °F (20 °C))
Power pole contact composition4 NO
Hold-in power consumption in4.5 VA (at 68 °F (20 °C))
Poles description4P
Utilisation categoryAC-1
IP degree of protectionIP20 VDE 0106
Mounting supportPlate Rail
Connections - terminalsscrew clamp terminals 1 0.002...0.006 in² (1.5...4 mm²)solid screw clamp terminals 1 0.001...0.006 in² (0.75...4 mm²)flexible without cable end screw clamp terminals 1 0.0005...0.004 in² (0.34...2.5 mm²)flexible with cable end screw clamp terminals 2 0.002...0.006 in² (1.5...4 mm²)solid screw clamp terminals 2 0.001...0.006 in² (0.75...4 mm²)flexible without cable end screw clamp terminals 2 0.0005...0.002 in² (0.34...1.5 mm²)flexible with cable end
Operating altitude6561.68 ft (2000 m) without derating
Depth2.2 in (57 mm)
Width3.5 in (90 mm)
Height2.3 in (58 mm)
Electrical durability0.16 Mcycles 20 A AC-1 <= 690 V
Mechanical durability5 Mcycles
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
RangeTeSys
CategoryUS10I1222327
Operating time10...20 ms coil energisation and NO closing 10...20 ms coil de-energisation and NO opening
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Heat dissipation1.3 W
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
Device short nameLC2K
Tightening torque7.08...11.5 lbf.in (0.8...1.3 N.m) screw clamp terminals Philips No 2 7.08...11.5 lbf.in (0.8...1.3 N.m) screw clamp terminals flat Ø 6 mm 7.08...11.5 lbf.in (0.8...1.3 N.m) screw clamp terminals pozidriv No 2
Device applicationControl
Device presentationPreassembled with reversing power busbar
Overvoltage categoryIII
Protective treatmentTC IEC 60068 TC DIN 50016
Contactor applicationResistive load
Mechanical robustnessShocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Associated fuse rating25 A gG at 25 A aM for power circuit
Maximum operating rate3600 cyc/h
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity110 A AC for power circuit conforming to IEC 60947
Ambient air temperature for storage-58...176 °F (-50...80 °C)
Ambient air temperature for operation-13...122 °F (-25...50 °C)

Product details

Mounting & wiring notes

Screw clamp terminals take 1 or 2 conductors from 0.34 to 4 mm². Tightening torque 0.8–1.3 N·m. IP20 finger-safe, V1 flame retardant per UL 94.

Sourcing

Active lifecycle stage.

Frequently asked questions

What are the key physical dimensions?

Depth 2.2 in (57 mm), width 3.5 in (90 mm), height 2.3 in (58 mm).

What compliance standards does it meet?

Meets EN/IEC 60947-4-1, GB/T 14048.4, UL 60947-4-1, CSA C22.2 No 60947-4-1, and JIS C8201-4-1. Flame retardance V1 per UL 94.

What is the coil voltage and frequency?

24 V AC, 50/60 Hz.

What is the rated breaking capacity?

110 A up to 440 V, 80 A at 500 V, 70 A at 660–690 V, per IEC 60947.

MPN
LC2K09004B7