What This Reversing Assembly Gives You
The LC2K09004E7 is a changeover contactor from the TeSys K series, prewired with a reversing power busbar and a mechanical interlock that prevents both contactors from closing at the same time. The control coil is 48 V AC 50/60 Hz; expected operating time for NO closing is 10–20 ms. Mounting is DIN rail or plate. Torque to 0.8–1.3 Nm. Power circuit impedance is 3 mOhm at 20 A, so heat dissipation stays at 1.3 W. That matters if you're packing multiple contactors in a small enclosure.
Fit and Mounting Notes
Mount on DIN rail or plate. Dimensions: 2.2 in deep, 3.5 in wide, 2.3 in tall. Screw terminals accept one or two conductors per clamp: 1.5–4 mm² solid or 0.75–4 mm² stranded without ferrule, up to 2.5 mm² with ferrule. Associated fuse recommendation: 25 A gG or 25 A aM on the power circuit. Maximum operating rate is 3600 cycles per hour. Mechanical durability 5 Mcycles; electrical durability at 20 A AC-1 is 0.16 Mcycles.