Skip to main content
Schneider Electric LC2K09004F7

Schneider LC2K09004F7 TeSys K Contactor, 110 V AC, 4P

MPNLC2K09004F7
Obsolete

Schneider Electric TeSys K LC2K09004F7, 4-pole changeover contactor, 110 V AC 50/60 Hz control circuit, preassembled reversing power busbar.

$36.83Ref. price · indicative, final on quote
Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K09004F7 key specifications
ParameterValue
Interlocking typeMechanical
Control circuit typeAC 50/60 Hz
Product or component typeChangeover contactor
Coil voltage110 V AC 50/60 Hz
VoltagePower circuit 600 V UL 508 Power circuit 690 V IEC 60947-4-1 Power circuit 600 V CSA C22.2 No 14
Control circuit voltage limitsOperational: 0.8...1.15 Uc (at Drop-out: 0.2...0.75 Uc (at <122 °F (50 °C))
[Ue] rated operational voltagePower circuit 690 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage8 kV
[Icw] rated short-time withstand current90 A 122 °F (50 °C) - 1 s for power circuit 85 A 122 °F (50 °C) - 5 s for power circuit 80 A 122 °F (50 °C) - 10 s for power circuit 60 A 122 °F (50 °C) - 30 s for power circuit 45 A 122 °F (50 °C) - 1 min for power circuit 40 A 122 °F (50 °C) - 3 min for power circuit 20 A 122 °F (50 °C) - >= 15 min for power circuit
Breaking capacity110 A at 220...230 V conforming to IEC 60947 110 A at 380...400 V conforming to IEC 60947 110 A at 415 V conforming to IEC 60947 110 A at 440 V conforming to IEC 60947 80 A at 500 V conforming to IEC 60947 70 A at 660...690 V conforming to IEC 60947
[Ie] rated operational current20 A (at <140 °F (60 °C)) at <= 440 V AC AC-1 for power circuit
[Ith] conventional free air thermal current20 A (at 140 °F (60 °C)) for power circuit

All specifications

LC2K09004F7 additional specifications
ParameterValue
Inrush power in30 VA (at 68 °F (20 °C))
Power pole contact composition4 NO
Hold-in power consumption in4.5 VA (at 68 °F (20 °C))
Poles description4P
Utilisation categoryAC-1
IP degree of protectionIP20 VDE 0106
Mounting supportPlate Rail
Connections - terminalsscrew clamp terminals 1 0.002...0.006 in² (1.5...4 mm²)solid screw clamp terminals 1 0.001...0.006 in² (0.75...4 mm²)flexible without cable end screw clamp terminals 1 0.0005...0.004 in² (0.34...2.5 mm²)flexible with cable end screw clamp terminals 2 0.002...0.006 in² (1.5...4 mm²)solid screw clamp terminals 2 0.001...0.006 in² (0.75...4 mm²)flexible without cable end screw clamp terminals 2 0.0005...0.002 in² (0.34...1.5 mm²)flexible with cable end
Operating altitude6561.68 ft (2000 m) without derating
Depth2.2 in (57 mm)
Width3.5 in (90 mm)
Height2.3 in (58 mm)
Electrical durability0.16 Mcycles 20 A AC-1 <= 690 V
Mechanical durability5 Mcycles
StandardsEN/IEC 60947-4-1 GB/T 14048.4 UL 60947-4-1 CSA C22.2 No 60947-4-1 JIS C8201-4-1
RangeTeSys
CategoryUS10I1222327
Operating time10...20 ms coil energisation and NO closing 10...20 ms coil de-energisation and NO opening
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
Heat dissipation1.3 W
Average impedance3 mOhm - Ith 20 A 50 Hz for power circuit
Device short nameLC2K
Tightening torque7.08...11.5 lbf.in (0.8...1.3 N.m) screw clamp terminals Philips No 2 7.08...11.5 lbf.in (0.8...1.3 N.m) screw clamp terminals flat Ø 6 mm 7.08...11.5 lbf.in (0.8...1.3 N.m) screw clamp terminals pozidriv No 2
Device applicationControl
Device presentationPreassembled with reversing power busbar
Overvoltage categoryIII
Protective treatmentTC IEC 60068 TC DIN 50016
Contactor applicationResistive load
Mechanical robustnessShocks contactor closed, on X axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Y axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor closed, on Z axis15 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on X axis6 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Y axis10 Gn for 11 ms IEC 60068-2-27 Shocks contactor opened, on Z axis10 Gn for 11 ms IEC 60068-2-27 Vibrations contactor closed4 Gn, 5...300 Hz IEC 60068-2-6 Vibrations contactor opened2 Gn, 5...300 Hz IEC 60068-2-6
Associated fuse rating25 A gG at 25 A aM for power circuit
Maximum operating rate3600 cyc/h
Safety reliability levelB10d = 1369863 cycles contactor with nominal load EN/ISO 13849-1 B10d = 20000000 cycles contactor with mechanical load EN/ISO 13849-1
Irms rated making capacity110 A AC for power circuit conforming to IEC 60947
Ambient air temperature for storage-58...176 °F (-50...80 °C)
Ambient air temperature for operation-13...122 °F (-25...50 °C)

Product details

The LC2K09004F7: Preassembled reversing contactor from the TeSys K line, 4-pole changeover with mechanical interlock, 110 V AC coil. AC-1 rated for resistive loads up to 20 A continuous. Screw-clamp terminals accept 1.5–4 mm² solid or stranded; mounts to plate or DIN rail.

The AC-1 utilisation category (resistive load) gives an electrical durability of 0.16 Mcycles at 20 A under 690 V. The 110 V AC control circuit draws 30 VA inrush at 20 °C, with operating time 10–20 ms for both closing and opening. Heat dissipation sits at 1.3 W – negligible for panel cooling calculations.

Tightening torque 0.8–1.3 N·m on the screw terminals. IP20 finger-safe protection per VDE 0106. Overvoltage category III suits fixed-installation distribution panels. Rated breaking capacity reaches 110 A at 380–440 V AC per IEC 60947 – margins well above the continuous rating.

Frequently asked questions

What is LC2K09004F7's listed depth?

The depth is 2.2 in (57 mm).

What is its range?

The part belongs to the TeSys range of contactors and starters.

What compliance documentation does this brand provide?

The contactor is listed against several standards: EN/IEC 60947-4-1, UL 60947-4-1, CSA C22.2 No 60947-4-1, JIS C8201-4-1, and GB/T 14048.4. These certifications cover most North American, European, and Asian panel requirements.

MPN
LC2K09004F7