Schneider Electric LC2K09103FE7 — Contactors

Schneider TeSys K LC2K09103FE7 Reversing Contactor, 9 A, 115

MPNLC2K09103FE7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤ 440 V 9 A, 1 NO, 115 V AC coil.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K09103FE7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC2K09103FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-1 AC-3 AC-4
LC2K09103FE7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K09103FE7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K09103FE7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

It carries a 115 V AC coil and one normally open auxiliary contact.

The contactor measures 57 mm deep by 90 mm wide by 58 mm high, with an IP20 degree of protection per VDE 0106 — suitable for enclosed panel mounting where fingers cannot contact live parts. Storage tolerance extends from -50 to 80 °C. Flame retardance meets UL 94 V1 and NF F 16-101/102 requirements, relevant for rail and transport applications.

Utilisation categories and motor control

Rated for utilisation categories AC-1 (resistive), AC-3 (squirrel-cage motors: starting, switching off running), and AC-4 (plugging, inching). The contactor is mechanically robust, with shock withstand up to 15 Gn on Y and Z axes (contactor closed) and vibration resistance of 4 Gn at 5–300 Hz.

Frequently asked questions

What is the closest alternative to LC2K09103FE7?

The TeSys K series has been superseded by the TeSys Deca range. However, no official direct replacement order code is listed. Pin-compatibility and mounting footprint must be verified against your existing panel layout before substitution. We can assist with cross-referencing upon RFQ.

What are the key ratings of LC2K09103FE7?

It is a 3-pole reversing contactor rated for AC-3 duty at 9 A / 440 V, with a 115 V AC coil and one NO auxiliary contact. Operational voltage is 690 V AC 50/60 Hz on the power circuit. Protection is IP20.

What compliance documentation is available for LC2K09103FE7?

The part carries UL 94 V1 flame retardance and NF F 16-101/102 compliance for rail applications. Protective treatment meets IEC 60068 and DIN 50016. Full RoHS/REACH/UL certification documents are typically available through Schneider Electric's documentation portal or upon request with an RFQ.

MPN