LC2K12013F7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationResistive load Motor control
LC2K12013F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-1 AC-3 AC-4
LC2K12013F7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K12013F7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K12013F7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The LC2K12013F7 is a TeSys K reversing contactor from Schneider Electric — a 3-pole unit rated for AC-3 duty at 12 A up to 440 V, with a 110 V AC coil and one NC auxiliary contact. The IP20 finger-safe enclosure (per VDE 0106) suits it for panel-mount applications where personnel access is controlled.

The AC-3 rating of 12 A at 440 V is the motor-switching current — this contactor handles reversing duty for a motor drawing up to that current under starting and running conditions. The 110 V AC coil matches standard control-voltage circuits in many industrial panels; verify your control transformer voltage before committing. The unit measures 90 mm wide, 58 mm tall, and 57 mm deep — compact enough for a crowded DIN-rail enclosure, but check the reversing busbar adds no extra width. Ambient operating range is -25 to 50 °C, with storage from -50 to 80 °C.

Frequently asked questions

What are the key dimensions?

Depth 57 mm, width 90 mm, height 58 mm.

What compliance documentation is available?

The part carries IP20 protection per VDE 0106, flame retardance V1 per UL 94, and meets NF F 16-101 and NF F 16-102 for rail fire safety. Ambient temperature ratings and shock/vibration robustness per IEC 60068 are specified.