Skip to main content
Schneider Electric LC2K1201R7 — Contactors

Schneider TeSys K LC2K1201R7 Reversing Contactor, 12 A AC-3,

MPNLC2K1201R7
Obsolete

Schneider Electric TeSys K reversing contactor, LC2K1201R7, 3P, AC-3 ≤440 V 12 A, 1 NC, 440 V AC coil, preassembled with reversing power busbar.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K1201R7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control Resistive load
LC2K1201R7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-1 AC-3 AC-4
LC2K1201R7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K1201R7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K1201R7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

It switches three poles (3 NO main contacts) and carries a single NC auxiliary contact. The 440 V AC coil pulls in on the control voltage common in European and Asian industrial panels. The AC-1 resistive rating covers heater banks or lighting circuits at the same current level. IP20 finger protection (VDE 0106) means it is safe for open-panel mounting inside an enclosure. Storage tolerance extends from -50 to 80 °C.

Sourcing Reality — Obsolete, Sourced to Order

Because it is a reversing contactor with a 440 V AC coil and a specific busbar assembly, a direct drop-in replacement from the current TeSys range may require a different coil voltage or a separate reversing kit. We can quote what is available on the open market; lead time and pricing vary by lot.

Frequently asked questions

What are the key electrical ratings for the LC2K1201R7?

It is a 3-pole reversing contactor rated 12 A in AC-3 duty at ≤440 V, with a 440 V AC coil. It also covers AC-1 (resistive) and AC-4 (plugging/inching) utilisation categories. The rated operational voltage on the power circuit is 690 V AC 50/60 Hz.

What is the physical size of this contactor?

Width 90 mm, height 58 mm, depth 57 mm. It is preassembled with a reversing power busbar, so the overall width is the same as a single contactor footprint.

What compliance standards does the LC2K1201R7 meet?

Flame retardance V1 per UL 94, plus NF F 16-101 and NF F 16-102 for rail. IP20 finger protection per VDE 0106. Protective treatment per IEC 60068 and DIN 50016. Shock and vibration tested per IEC 60068-2-27 and IEC 60068-2-6.

MPN