The 115 V AC coil is standard for North American control circuits. Operating temperature range is -25 to 50 °C, storage from -50 to 80 °C, and it runs without derating up to 2000 m altitude — typical for most industrial sites.
TeSys K LC2K12103FE7 reversing contactor, 3P, 12 A AC-3, 115
MPNLC2K12103FE7
Active
Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 12 A, 1 NO auxiliary, 115 V AC coil, IP20, preassembled with reversing power busbar.
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Reversing contactor |
| Series / range | TeSys |
| Application | Resistive load Motor control |
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit |
| Utilisation category | AC-1 AC-4 AC-3 |
| Parameter | Value |
|---|---|
| Pole configuration | 3P |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to VDE 0106 |
| Operating altitude | 2000 m without derating |
| Mechanical robustness | Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Protective treatment / pollution degree | TC conforming to IEC 60068 TC conforming to DIN 50016 |
| Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Parameter | Value |
|---|---|
| Width | 90 mm |
| Height | 58 mm |
| Depth | 57 mm |
Product details
Frequently asked questions
What are the key ratings for this reversing contactor?
It is a 3-pole reversing contactor rated AC-3 at 12 A up to 440 V, with a 115 V AC coil. It comes preassembled with the reversing power busbar. IP20 protected, operating temperature -25 to 50 °C.
What compliance documentation does this part carry?
It is UL 94 V1 flame retardant, compliant with NF F 16-101 and NF F 16-102 for rail applications, and IP20 per VDE 0106. The protective treatment meets IEC 60068 and DIN 50016.
MPN
LC2K12103FE7