It carries three normally-open power poles and one normally-closed auxiliary contact, with a 220…230 V AC coil. The same contactor also carries an AC-4 utilisation category for plugging and inching applications, where the motor is reversed or stopped by reversing the phase sequence while the rotor is still spinning. The power circuit is rated for 690 V AC 50/60 Hz, giving headroom for 400 V or 480 V line supplies. The IP20 degree of protection (per VDE 0106) means it is finger-safe for panel installation but not protected against moisture ingress — it belongs inside an enclosure.

Schneider TeSys K LC2K16017M72 Reversing Contactor, 3P, 16 A
Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NC, 220…230 V AC, IP20, 57 mm depth.
Specifications
| Parameter | Value |
|---|---|
| Product / component type | Reversing contactor |
| Series / range | TeSys |
| Application | Motor control |
| Parameter | Value |
|---|---|
| Rated operational voltage (Ue) | Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit |
| Utilisation category | AC-4 AC-3 |
| Parameter | Value |
|---|---|
| Pole configuration | 3P |
| Parameter | Value |
|---|---|
| IP degree of protection | IP20 conforming to VDE 0106 |
| Operating altitude | 2000 m without derating |
| Mechanical robustness | Shocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6 |
| Protective treatment / pollution degree | TC conforming to IEC 60068 TC conforming to DIN 50016 |
| Flame retardance | V1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102 |
| Parameter | Value |
|---|---|
| Width | 90 mm |
| Height | 58 mm |
| Depth | 57 mm |
Product details
Frequently asked questions
What are the key ratings for this reversing contactor?
It is a 3-pole reversing contactor rated AC-3 ≤440 V at 16 A, with a 220…230 V AC coil and one NC auxiliary contact. The power circuit is rated for 690 V AC 50/60 Hz. IP20 finger-safe protection, operating temperature -25…50 °C, and altitude 2000 m without derating.
What compliance documentation does Schneider provide for the LC2K16017M72?
The contactor carries UL 94 V1 flame retardance and meets NF F 16-101/102 for rail fire resistance. It is IP20 per VDE 0106. Shock and vibration testing follows IEC 60068-2-27 and IEC 60068-2-6. Protective treatment complies with IEC 60068 and DIN 50016. RoHS/REACH status is not listed in this record; verify with the manufacturer for current declarations.