Schneider Electric LC2K1601M7 — Contactors

Schneider Electric LC2K1601M7 TeSys K Reversing Contactor, 1

MPNLC2K1601M7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NC, 220-230 V AC coil, preassembled with reversing power busbar.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K1601M7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K1601M7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4
LC2K1601M7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K1601M7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K1601M7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC2K1601M7 is a TeSys K reversing contactor — a 3-pole device rated AC-3 ≤440 V at 16 A, with a 220-230 V AC coil and one NC auxiliary contact. Rated operational voltage on the power circuit is 690 V AC 50/60 Hz, and the utilisation categories AC-3 and AC-4 cover both normal starting and plugging/inching duty. The 16 A AC-3 rating at ≤440 V is the figure that governs motor switching — it handles squirrel-cage motors up to roughly 7.5 kW at 400 V three-phase.

If your customer's AVL or AML lists the LC2K1601M7 specifically, a deviation or change request will be needed to move to a current-production reversing contactor from the TeSys range. The physical footprint (57 mm depth, 90 mm width, 58 mm height) and the preassembled busbar arrangement are the dimensions any substitute must match.

Frequently asked questions

What are the key ratings for the LC2K1601M7?

It is a 3-pole reversing contactor rated AC-3 ≤440 V at 16 A, with a 220-230 V AC coil and one NC auxiliary contact. The power circuit is rated 690 V AC 50/60 Hz. It comes preassembled with a reversing power busbar.

What compliance documentation is available for this part?

The part carries V1 flame retardance per UL 94 and compliance with NF F 16-101 and NF F 16-102 railway fire standards. IP20 protection is per VDE 0106. Shock and vibration testing follows IEC 60068-2-27 and IEC 60068-2-6. Protective treatment conforms to IEC 60068 and DIN 50016.

MPN
LC2K1601M7