Skip to main content
Schneider Electric LC2K1601Q7 — Contactors

Schneider TeSys K LC2K1601Q7 reversing contactor, 3P, 16 A A

MPNLC2K1601Q7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NC, 380-400 V AC 50/60 Hz coil, IP20 finger-safe.

StockContact for availability
Lead time3-5 Days wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC2K1601Q7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC2K1601Q7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3

Contacts & Poles

LC2K1601Q7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC2K1601Q7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Mechanical

LC2K1601Q7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

It's rated for AC-3 duty up to 16 A at ≤440 V, with a 380-400 V AC 50/60 Hz coil, and carries one NC auxiliary contact. The AC-3 utilization category means it's built for starting and stopping squirrel-cage motors on-load — the standard duty for reversing contactors in conveyor, pump, and fan applications. The 16 A rating at ≤440 V covers motors up to roughly 7.5 kW at 400 V, depending on the motor's full-load current.

The contactor measures 90 mm wide × 58 mm high × 57 mm deep, with IP20 finger-safe protection per VDE 0106 — no extra shrouding needed inside an enclosed panel. Rated for operation up to 2000 m altitude without derating — fine for most industrial sites outside high-altitude installations.

Mechanical robustness and compliance

The contactor is tested to IEC 60068-2-27 for shock and IEC 60068-2-6 for vibration. With the contactor closed, it withstands 10 Gn on Y and Z axes, 6 Gn on X — relevant for equipment mounted on vibrating machinery or near impact zones. Vibration resistance is 4 Gn closed, 2 Gn open across 5-300 Hz. Flame retardance is V1 per UL 94, and also meets NF F 16-101 and NF F 16-102 requirements — useful for rail and transport applications where fire-smoke-toxicity standards apply. Protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance.

The LC2K1601Q7 is an active, current-production part in the TeSys K range. For BOM-freeze or compliance audits, the manufacturer maintains the full declaration package (RoHS, REACH, UL, IEC) on this order code. The part is specified directly into motor-reversing circuits in panels, conveyors, and HVAC equipment.

Frequently asked questions

What is the closest alternative to the LC2K1601Q7 in the same family?

The LC2K1601Q7 is a reversing contactor with a 380-400 V AC coil. The standard TeSys K reversing contactor with the same 16 A AC-3 rating but a different coil voltage (e.g., 230 V AC or 24 V DC) would be the closest functional sibling — the coil voltage is the only difference that changes the order code. A non-reversing single contactor from the same TeSys K range (LC1K series) shares the same footprint and aux contact layout but lacks the reversing busbar preassembly.

What are the key ratings for the LC2K1601Q7?

AC-3 rated operational current is 16 A at ≤440 V. Coil voltage is 380-400 V AC 50/60 Hz. It has 3 NO power poles and 1 NC auxiliary contact. Rated operational voltage for the power circuit is 690 V AC. IP20 finger-safe protection. Dimensions: 90 × 58 × 57 mm.

What compliance documentation is available for the LC2K1601Q7?

The contactor carries V1 flame retardance per UL 94, meets NF F 16-101 and NF F 16-102 for rail applications, and has protective treatment per IEC 60068 and DIN 50016. IP20 per VDE 0106. Standard manufacturer declarations for RoHS, REACH, and CE are available for this order code.

MPN
LC2K1601Q7