It switches a 3-phase motor up to 16 A in AC-3 duty (≤440 V) and carries a 24 V AC coil. The 3 NO power poles handle forward/reverse interlocking without external wiring.
The AC-3 rating at 16 A is the motor-switching current — the contactor is sized for a 3-phase motor drawing up to 16 A under full load, typical for a 7.5 kW motor at 400 V. The 24 V AC coil means the control transformer or PLC output must supply 24 V AC, not DC; verify your control voltage before wiring. IP20 (finger-safe terminals) suits enclosed panel mounting, not open washdown areas. The 57 mm depth fits standard 90 mm wide DIN-rail enclosures with room for gland plates.
Operates without derating up to 2000 m altitude. Vibration resistance: 4 Gn closed, 2 Gn open (5–300 Hz). Shock tolerance: 10–15 Gn depending on axis and contactor state. Flame retardance meets UL 94 V1 and NF F 16-101/102, so it passes rail and industrial fire-safety checks.