The Schneider Electric LC2K16105C7 is a TeSys K reversing contactor — a 3-pole, 3 NO power pole unit rated AC-3 at 16 A up to 440 V, with a 36 V AC coil and one normally open auxiliary contact. It comes preassembled with the reversing power busbar, so the mechanical interlock and bus wiring are already in place for a reversing motor starter.
The AC-3 rating of 16 A at ≤440 V governs the contactor's ability to switch motor loads. The 36 V AC coil requires a 36 V AC control supply. Dimensions are 57 mm deep, 90 mm wide, and 58 mm tall. Operating altitude is 2000 m without derating.
The contactor carries V1 flame retardance per UL 94 and meets NF F 16-101/-102 for rail-vehicle fire behavior. Protective treatment is TC per IEC 60068 and DIN 50016 (resistance to tropical climates). Shock and vibration ratings are documented per IEC 60068-2-27 and IEC 60068-2-6 — the contactor holds closed through 10 Gn on Y and Z axes, 6 Gn on X when open.