Skip to main content
Schneider Electric LC2K16105E7 — Contactors

Schneider TeSys K LC2K16105E7 Reversing Contactor, 16 A, 48

MPNLC2K16105E7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 48 V AC coil, preassembled with reversing power busbar.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K16105E7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16105E7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3
LC2K16105E7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16105E7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16105E7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The AC-3 rating of 16 A at 440 V governs motor switching — that is the current the contactor can make and break under full-load motor starting. The 48 V AC coil pull-in voltage must match the control transformer tap; a coil outside ±10 % of nominal may not hold closed under brownout. IP20 finger-safe terminals (VDE 0106) mean it is intended for enclosed panel mounting, not exposed washdown areas. The V1 flame-retardance rating per UL 94 and NF F 16-101 is a material-level safety property for rail and industrial enclosures.

The 90 mm width × 58 mm height × 57 mm depth footprint clips onto standard DIN rail. The preassembled reversing busbar saves one wiring step — incoming line lands on the common terminals, and the two contactor coils are interlocked via the built-in mechanical linkage so both cannot close simultaneously. Operating altitude is 2000 m without derating; above that, the dielectric withstand drops and the contactor must be de-rated per IEC 60947.

Frequently asked questions

What are the key ratings for this reversing contactor?

AC-3 motor-switching rating of 16 A at 440 V, 48 V AC coil, 3 NO main poles, IP20 finger-safe protection, and V1 flame retardance per UL 94.

How do I source this obsolete part?

Through surplus or broker channels. We source it to order against an RFQ, verifying condition and traceability before shipment.

MPN
LC2K16105E7