Skip to main content
Schneider Electric LC2K16105U7 — Contactors

TeSys K LC2K16105U7 Reversing Contactor, 3P, AC-3 16A, 230-2

MPNLC2K16105U7
Active

Schneider Electric TeSys K reversing contactor, 3P, AC-3 ≤440 V 16 A, 1 NO, 230…240 V AC coil, IP20.

Source DocumentedChannel stated on listing & quote
Condition PhotosReal unit photos / video on request
WhatsApp AnswersFast human replies for machine-down parts
Worldwide DispatchDHL/FedEx — transit quoted per order
Independent China distributor & sourcing agent· Listing updated Sep 2026

Specifications

LC2K16105U7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control
LC2K16105U7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3
LC2K16105U7 — Contacts & Poles
ParameterValue
Pole configuration3P
LC2K16105U7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102
LC2K16105U7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

Its headline rating is AC-3 duty at 16 A up to 440 V — the current it can switch under motor starting conditions (inrush and breaking) without welding contacts.

The contactor measures 90 mm wide by 58 mm high by 57 mm deep.

Mechanical and environmental robustness

Rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6: contactor closed withstands 10 Gn on X axis, 15 Gn on Y and Z axes (11 ms half-sine); open state withstands 6 Gn on X, 10 Gn on Y and Z. Vibration resistance is 4 Gn closed, 2 Gn open across 5–300 Hz. Flame retardance meets V1 per UL 94 and NF F 16-101/102. Protective treatment conforms to IEC 60068 and DIN 50016 for corrosion resistance.

Frequently asked questions

What are the key ratings of the LC2K16105U7?

It is a 3-pole reversing contactor rated AC-3 at 16 A up to 440 V, with a 230…240 V AC coil. The IP20 enclosure protects against finger contact in a panel.

What is the physical size of the LC2K16105U7?

Width 90 mm, height 58 mm, depth 57 mm.

What compliance documentation is available for the LC2K16105U7?

The part carries V1 flame retardance per UL 94 and conforms to NF F 16-101/102. Protective treatment meets IEC 60068 and DIN 50016. No RoHS or REACH statements are in the record.

MPN
LC2K16105U7