Skip to main content
Schneider Electric LC2K16107F7 — Contactors

Schneider TeSys K LC2K16107F7 Reversing Contactor, 3P, 16 A,

MPNLC2K16107F7
Obsolete

Schneider Electric TeSys K reversing contactor, 3P, AC-3 <= 440 V 16 A, 1 NO, 110 V AC coil, preassembled with reversing power busbar.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC2K16107F7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC2K16107F7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3

Contacts & Poles

LC2K16107F7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC2K16107F7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Mechanical

LC2K16107F7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The Schneider Electric LC2K16107F7 is a TeSys K reversing contactor, 3P, rated for AC-3 duty at 16 A up to 440 V and AC-4 duty, with a 110 V AC coil. The 3 NO power poles handle the forward and reverse circuits, and the single NO auxiliary contact provides feedback or a holding circuit.

The IP20 finger-safe terminals (per VDE 0106) suit it for enclosed control panels where personnel access is restricted. Operating altitude is 2000 m without derating — fine for most industrial sites.

Frequently asked questions

What is the closest alternative to the LC2K16107F7?

Schneider has not published an official successor order code for this part. A replacement must be selected based on the original ratings: reversing contactor, 3P, AC-3 16 A at 440 V, 110 V AC coil. The TeSys K series includes active reversing contactors with similar footprints; verify coil voltage and auxiliary contact configuration before substituting.

What are the key ratings of the LC2K16107F7?

It is a 3-pole reversing contactor rated AC-3 at 16 A up to 440 V, with a 110 V AC coil. Power circuit rated 690 V AC 50/60 Hz. Includes one NO auxiliary contact. Preassembled with reversing power busbar.

MPN