Schneider Electric LC2K16107FC72 — Contactors

Schneider TeSys K LC2K16107FC72 Reversing Contactor, 3P, 16

MPNLC2K16107FC72
Active

Schneider Electric TeSys K reversing contactor, LC2K16107FC72, 3P, AC-3 <=440 V 16 A, 1 NO auxiliary, 127 V AC coil, IP20, preassembled with reversing busbar.

StockContact for availability
Lead timeIn Stock wk
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC2K16107FC72 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC2K16107FC72 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-3 AC-4

Contacts & Poles

LC2K16107FC72 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC2K16107FC72 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Mechanical

LC2K16107FC72 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The LC2K16107FC72 is a TeSys K reversing contactor from Schneider Electric — a 3-pole unit rated AC-3 at 16 A up to 440 V, with a 127 V AC coil and one normally open auxiliary contact. The AC-3 rating is the motor-switching duty class per IEC 60947-4-1: 16 A means it can handle a 3-phase induction motor drawing that current during starting and stopping, which is the real-world load for reversing starters on conveyors, pumps, or fans. The part ships preassembled with the reversing power busbar, so you don't need to source a separate mechanical interlock kit for the forward/reverse pair.

Fit and integration details

The 127 V AC coil is a common control voltage in older North American installations and some industrial sites running 120 V control transformers — verify your control circuit matches before wiring.

Mechanical and environmental robustness

Rated for shock and vibration per IEC 60068-2-27 and IEC 60068-2-6: contactor stays closed under 10 Gn on Y and Z axes, 6 Gn on X when open. Vibration tolerance is 4 Gn closed, 2 Gn open across 5–300 Hz. That's enough for most industrial machinery, including conveyors and compressors mounted near the source. Flame retardance meets UL 94 V1 and NF F 16-101/102, which is relevant for rail and transport applications where fire-smoke-toxicity requirements apply.

Frequently asked questions

What is the closest pin-compatible alternative to LC2K16107FC72 in this component family?

Within the TeSys K series, the closest sibling is a reversing contactor with the same 3-pole AC-3 16 A rating but a different coil voltage. The LC2K16107FC72 uses a 127 V AC coil; if your control voltage differs, match the coil code suffix. No direct pin-compatible substitute outside the series is listed — the TeSys K footprint is specific to this family.

What is LC2K16107FC72's listed depth (57 mm) on this component line?

The depth is 57 mm, which is the dimension from the mounting surface to the front of the contactor body — not including the coil terminals or auxiliary contact block if added.

What is LC2K16107FC72's listed range (TeSys) on this component line?

The range is TeSys, specifically the TeSys K sub-family of compact contactors and reversing contactors for motor control up to 16 A AC-3.

What compliance documentation does this brand provide for LC2K16107FC72 (RoHS, REACH, UL, IEC)?

The part carries IEC 60947-4-1 compliance for contactors, UL 94 V1 flame retardance, and IP20 per VDE 0106. RoHS and REACH declarations are standard for Schneider TeSys products but are not explicitly listed in this record — confirm with the manufacturer's documentation portal.