Skip to main content
Schneider Electric LC2K16107FE7 — Contactors

TeSys K LC2K16107FE7 Reversing Contactor, 3P, AC-3 16 A, 115

MPNLC2K16107FE7
Obsolete

Schneider Electric TeSys K reversing contactor, LC2K16107FE7, 3P, AC-3 ≤440 V 16 A, 1 NO, 115 V AC coil, IP20, 57 mm depth.

StockContact for availability
MOQ1 pcs
Sourced new & surplus through independent channelsAuthenticity-screened · ESD-safe packingListing updated Jul 2026
How we verify every order →

Specifications

Identification

LC2K16107FE7 — Identification
ParameterValue
Product / component typeReversing contactor
Series / rangeTeSys
ApplicationMotor control

Ratings & Performance

LC2K16107FE7 — Ratings & Performance
ParameterValue
Rated operational voltage (Ue)Power circuit: 690 V AC 50/60 Hz Signalling circuit: 10 MOhm for signalling circuit
Utilisation categoryAC-4 AC-3

Contacts & Poles

LC2K16107FE7 — Contacts & Poles
ParameterValue
Pole configuration3P

Environmental

LC2K16107FE7 — Environmental
ParameterValue
IP degree of protectionIP20 conforming to VDE 0106
Operating altitude2000 m without derating
Mechanical robustnessShocks contactor closed, on X axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Y axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor closed, on Z axis: 15 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on X axis: 6 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Y axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Shocks contactor opened, on Z axis: 10 Gn for 11 ms conforming to IEC 60068-2-27 Vibrations contactor closed: 4 Gn, 5...300 Hz conforming to IEC 60068-2-6 Vibrations contactor opened: 2 Gn, 5...300 Hz conforming to IEC 60068-2-6
Protective treatment / pollution degreeTC conforming to IEC 60068 TC conforming to DIN 50016
Flame retardanceV1 conforming to UL 94 Requirement 2 conforming to NF F 16-101 Requirement 2 conforming to NF F 16-102

Mechanical

LC2K16107FE7 — Mechanical
ParameterValue
Width90 mm
Height58 mm
Depth57 mm

Product details

The LC2K16107FE7 is a TeSys K reversing contactor from Schneider Electric — a 3-pole unit preassembled with a reversing power busbar, rated for AC-3 duty at ≤440 V and 16 A, with a 115 V AC coil and one normally-open auxiliary contact. The AC-3 rating means it handles starting and stopping of squirrel-cage motors under load — the 16 A figure governs the maximum motor current it can switch in that duty, not a resistive-heater load. IP20 finger protection (VDE 0106) suits it for enclosed panel mounting where the contactor is not exposed to dust or washdown.

Integration notes

The contactor is preassembled with a reversing power busbar, which simplifies wiring for motor reversing circuits — the mechanical interlock is built in, so you don't need an external interlock module. Flame retardance meets UL 94 V1 and NF F 16-101/102, relevant for rail or industrial control panels with fire-safety requirements.

Frequently asked questions

What are the key ratings for this reversing contactor?

AC-3 duty at ≤440 V 16 A, 115 V AC coil, 3 poles, 1 NO auxiliary contact, IP20 protection.

What is the depth of the LC2K16107FE7?

57 mm.

What series does this contactor belong to?

TeSys K.

MPN
LC2K16107FE7